6.1.2 IE FM FISCO (fieldbus intrinsically safe concept)
Certifikat
3011568
Standar-
der
Factory Mutual (FM)-klass 3600:1998, Factory Mutual (FM)-
klass 3610:2010, Factory Mutual (FM)-klass 3611:2004, Facto-
ry Mutual (FM)-klass 3810:2005, ANSI/ISA 60079-0:2009,
ANSI/ISA 60079-11:2009, NEMA 250:1991, IEC 60529:2011
Märkdata
IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C ≤ T
a
≤ +60 °C); NI CL I,
DIV 2, GP A, B, C, D; T4A(–50 °C ≤ T
a
≤ +85 °C); T5(–50 °C ≤ T
a
≤ +70 °C) vid installation i enlighet med Rosemount-ritning
00848-4404.
6.1.3 N5 Explosionssäker och dammgnistsäker
Certifikat
3011568
Standarder
Factory Mutual (FM)-klass 3600:1998, Factory Mutual (FM)-
klass 3611:2004, Factory Mutual (FM)-klass 3810:2005,
ANSI/ISA 60079-0:2009, NEMA 250:1991, IEC 60529:2011
Märkdata
NI CL I, DIV 2, GP A, B, C, D; DIP CL II/III, DIV 1, GP E, F, G;
T4A(–50 °C ≤ T
a
≤ +85 °C); T5(–50 °C ≤ T
a
≤ +70 °C) vid instal-
lation enligt Rosemount-ritning 00848-4404; typ 4X
6.1.4 NK Gnistfri
Certifikat
3011568
Standarder
Factory Mutual (FM)-klass 3600:1998, Factory Mutual (FM)-
klass 3611:2004, Factory Mutual (FM)-klass 3810:2005,
ANSI/ISA 60079-0:2009, NEMA 250:1991, IEC 60529:2001
Märkdata
NI CL I, DIV 2, GP A, B, C, D; T4A(–50 °C ≤ T
a
≤ +85 °C); T5(–50
°C ≤ T
a
≤ +70 °C) vid installation enligt Rosemount-ritning
00848-4404
Anm
Endast N5 och NK är giltiga med S002-tillvalet.
Tabell 6-1. Parametrar för MAI-block
Fältbuss (ingång) FISCO (fieldbus in-
trinsically safe
concept) (inmat-
ning)
Gnistfri (ingång) Sensorfältanslut-
ning (utgång)
V
MAX
= 30 V V
MAX
= 17,5 V
MAX
= 42,4 V
OC
= 12,5 V
I
MAX
= 300 mA I
MAX
= 380 mA C
i
= 2,1 nF I
SC
= 4,8 mA
Snabbstartsguide Maj 2019
20 Rosemount 848T