12
ACS 550 Variable speed drive
9902 Applic. macro 1 = ABB standard
9802 Comm prot sel 1 = Std modbus
1001 Ext1 commands 10 = Comm
1103 Ref1 select 8 = Comm
1604 Fault reset sel 8 = Comm
If remote drive reset is enabled in EC 531
5302 EFB station ID (Node address) Unique slave ID corresponding to EC 531 setting
5303 EFB baud rate Same as EC 531
5304 EFB parity Same as EC 531
5305 EFB ctrl. prole 0 = ABB Drv Lim
For PSTx the ”Poll interval” in controller must be set to 0 second (as fast as possible) to avoid drive
trip, this as the PSTx have an internal (not adjustable) eldbus timeout of 0.1 second, before drive
trips and stops the motor.
With this short timeout, only one corrupt Modbus message may trip the drive. Adjust drive setting
19.04 to the safety level required for your application.
PSTx Soft starter
12.01 Com3 function Modbus RTU slave
12.02 FB interface connector Modbus RTU
12.03 Fieldbus control Off if “Monitor” On if “Control ON/OFF” over eldbus
12.04 Fieldbus address Unique slave ID corresponding to EC 531 setting
12.09 FB baud rate* Same as EC 531 limited to 9600 or 19200
12.10 FB parity Same as EC 531
12.11 FB stop bits Same as EC 531
12.12 Fieldbus DI 1 Run status (default)
12.13 Fieldbus DI 2 TOR status (default)
12.14 Fieldbus DI 3 Line (default)
12.15 Fieldbus DI 4 Phase sequence (default)
12.16 Fieldbus DI 5 Start feedback (default)
12.17 Fieldbus DI 6 Stop feedback (default)
12.18 Fieldbus DI 7 Event group 0 status (default)
12.19 Fieldbus DI 8 Event group 1 status (default)
12.20 Fieldbus DI 9 Event group 2 status (default)
12.21 Fieldbus DI 10 Event group 0 status (default)
12.22 Fieldbus AI 1 Phase L1 current
12.23 Fieldbus AI 2 Phase L2 current
12.24 Fieldbus AI 3 Phase L3 current
12.25 Fieldbus AI 4 Motor current
12.26 Fieldbus AI 5 Mains frequency
12.27 Fieldbus AI 6 Mains voltage
12.28 Fieldbus AI 7 Apparent power
12.29 Fieldbus AI 8 Active power
sv
81307147F