GB - BESB – Product information
1.1 Main parts............................................................................................................. 4
1.2 Transport .............................................................................................................. 5
1.3 Fitting.................................................................................................................... 5
1.3.1 Fitting indoors ............................................................................................... 5
1.3.2 Fitting outdoors (OD)..................................................................................... 6
1.3.3 Fitting the mounting bars............................................................................... 6
1.4 Wiring.................................................................................................................... 7
1.4.1 Ventilator with EC control.............................................................................. 8
1.4.2 Troubleshooting EC control......................................................................... 11
1.5 Connecting to duct system:.............................................................................. 12
1.6 Airflow measurement ........................................................................................ 13
1.7 Service and cleaning ......................................................................................... 14
1.8 Environmental declaration................................................................................ 14
DK - BESB - Produktvejledning
1.1 Opbygning.......................................................................................................... 16
1.2 Transport ............................................................................................................ 17
1.3 Montage .............................................................................................................. 17
1.3.1 Indendørs placering .................................................................................... 17
1.3.2 Udendørs placering (OD) ............................................................................ 18
1.3.3 Montage af bæreskinner ............................................................................. 18
1.4 El-tilslutning ....................................................................................................... 19
1.4.1 Ventilatorer med EC-styring ........................................................................ 20
1.4.2 Fejlfinding for styring ................................................................................... 23
1.5 Kanaltilslutning.................................................................................................. 24
1.6 Luftmængdemåling............................................................................................ 25
1.7 Service og rengøring......................................................................................... 26
1.8 Miljødeklaration.................................................................................................. 27
DE - BESB - Betriebsanleitung
1.1 Aufbau................................................................................................................. 28
1.2 Transport ............................................................................................................ 29
1.3 Montage .............................................................................................................. 29
1.3.1 Aufstellung in Innenräumen ........................................................................ 29
1.3.2 Aufstellung im Freien (OD).......................................................................... 30
1.3.3 Montage von Tragschienen......................................................................... 30
1.4 Elektrischer Anschluss ..................................................................................... 31
1.4.1 Ventilatoren mit EC-Automatik .................................................................... 32
1.4.2 Fehlersuche bei EC-Automatik.................................................................... 35
1.5 Kanalanschluss.................................................................................................. 36
1.6 Luftmengenmessung......................................................................................... 37
1.7 Wartung und Reinigung ....................................................................................38
1.8 Umweltdeklaration............................................................................................. 39
NO - BESB - Produktveiledning
1.1 Oppbygning........................................................................................................ 40
1.2 Transport ............................................................................................................ 41
1.3 Montering............................................................................................................ 41
1.3.1 Innendørs plassering .................................................................................. 41
1.3.2 Utendørs plassering (OD) ........................................................................... 42
1.3.3 Montering av bæreskinner........................................................................... 42
1.4 Elektrisk tilkobling............................................................................................. 43
1.4.1 Vifter med EC-styring .................................................................................. 44
1.4.2 Feilsøking for EC-styring............................................................................. 47
1.5 Kanaltilkobling ................................................................................................... 48
1.6 Luftmengdemåling............................................................................................. 49
1.7 Service og rengjøring........................................................................................ 50
1.8 Miljødeklarasjon................................................................................................. 51
BESB 3006652-2023-09.27.fm
3/64
SE – BESB – Produkthandbok
1.1 Konstruktion....................................................................................................... 52
1.2 Transport ............................................................................................................ 53
1.3 Montering............................................................................................................ 53
1.3.1 Inomhusmontering ...................................................................................... 53
1.3.2 Placering utomhus (OD).............................................................................. 54
1.3.3 Montering av bärskenor............................................................................... 54
1.4 Elanslutning ....................................................................................................... 55
1.4.1 Fläktar med EC-styrning.............................................................................. 56
1.4.2 Felsökning för EC-styring............................................................................ 59
1.5 Kanalanslutning................................................................................................. 60
1.6 Luftmengdemåling............................................................................................. 60
1.7 Service og rengjøring........................................................................................ 61
1.8 Miljödeklaration.................................................................................................. 62
BESB 3006652-2023-09.27.fm GB - BESB – Product information
4/64
1. GB - BESB – Product information
EXHAUSTO BESB box ventilators are used in air supply and extraction systems.
The ventilator is not to be used to transport solid particles, nor in areas
where there is a risk of explosive gases.
The ventilator must not be started with the service door open.
Description BESB is available in four different sizes, is completely insulated, and has a low-noise
centrifugal fan with cast aluminium backward-bent blades (B-impeller):
• BESB250-4-1EC2
• BESB315-4-1EC2
• BESB400-4-1EC2
• BESB500-4-1EC2
• BESB500-4-3EC
The ventilator has an internal insulated housing and an external cabinet, both made of
sheet aluminium.
Main components
Min. operating temperature: -12°C max. operating temperature +80°C
Ambient temperature when running: min. -30°C max. +40°C
1.1 Main parts
Pos. Part
a Cabinet
b Service door
c Motor
d B-impeller
e Fan housing
f Locking screws (supplied with screwdriver)
g Handle
h Mounting bars with vibration damper
i Self-tapping screws
j Hinges
k EC control/terminal box
m Air flow measuring probes (not included with BESB250)
ab
c
d
e
ih
k
-12°C - +80°C
-30°C - +40°C
+
-
m
g
f
j
RD13284-01
BESB 3006652-2023-09.27.fm GB - BESB – Product information
5/64
The ventilator is delivered packaged and can be transported on a pallet. Once unpacked
the ventilator should be handled carefully, especially the spigots etc. Deformation could
result in internal damage to the moving parts.
If there is not a lot of space to move the ventilator, the service door can be dismounted
as shown in section 1.1.
NB The ventilator must not be lifted using the service door handle.
Weight
1.3.1 Fitting indoors
There are various ways of fitting the
ventilator indoors.
With methods B and D the service door
must be kept in the open position during
service. A safety fitting for this purpose can
be supplied (including an assembly kit).
If the ventilator is to run intermittently, there
is a risk of condensation in the motor.
Therefore, use mounting method A or B
only.
Service access Wherever the ventilator is fitted, there
should be space enough to be able to open
the service door to an angle of approx. 80°
and to access the locking screws.
Warning The motor must never be placed vertically under the cabinet and the
motor and EC control must never be covered or they will overheat.
1.2 Transport
BESB 250 315 400 500
kg 52 57 73 88 91 (-3)
1.3 Fitting
RD11356-01
RD13304-01
D
D
BESB 3006652-2023-09.27.fm GB - BESB – Product information
6/64
1.3.2 Fitting outdoors (OD)
OD type ventilators are designed for
outdoor use and can be used for
transport of air in the temperature range
up to 200°C. This version is also fitted
with a drain in installation method "A"
A and B fitting methods should be
used for outdoor fitting. Fitting
methods C and D require a specially
designed ventilator — contact
EXHAUSTO.
All exterior seams, including spigots
have been jointed to prevent water from
getting inside.
The cabinet is class C4 DS/EN ISO12
944.2 certified and designed for
outdoors.
Service access Wherever the ventilator is fitted, there should
be space enough to be able to open the
service door to an angle of approx. 80° and to
access the locking screws.
1.3.3 Fitting the mounting bars
Mounting should be done on a stable vibration-resistant base, to minimise any
vibration that might be caused by the ventilator. A cement slab placed on a
wooden base construction is recommended.
Fit the mounting bars on the cabinet with the supplied fitting screws. The cabinet
has holes already bored for fitting method A.
BESB400 and 500: When using fitting method B for BESB400 and 500, holes
(Ø16 - Ø20) are bored in the cabinet for the fitting of the mounting bars.
Fit the mounting bars while the ventilator is on the pallet.
Sit the ventilator on the supporting base. Do not fasten the ventilator to the base.
A
B
C
D
RD13304-01
D
D
RD13303-01
BESB 3006652-2023-09.27.fm GB - BESB – Product information
7/64
General
The wiring must only be done by a qualified electrician.
The fan and motor specifications are listed
on the type-plates.
Max. fuse rating = 13 Amp.
Max. short circuit current is 10 kA
At start-up and during the initial adjustment of the fan, it is important to control the
direction of rotation of the motor and to check the motor current does not exceed the
manufacturer’s recommended operating current for the motor (to avoid damaging the
motor).
Isolation switch EXHAUSTO A/S would like to draw attention to the fact that, in
accordance with the EU's Machine Directive (appendix 1) all fan
systems shall include a isolation switch.
The isolation switch must ...
be lockable or positioned in plain sight in the immediate vicinity of the fan
be able to disconnect all poles from the supply voltage
— contact distance of at least 3 mm in each pole
Set up as isolation switch in accordance with standard IEC 60947-1 or
IEC 60947-3.
The isolation switch is not supplied by EXHAUSTO.
Lightning
conductor
Any lightning conductor connected to the fan must be in accordance with applicable
regulations and legislation.
1.4 Wiring
RD13301-01
If the fuse is a ...it must have the characteristic
melting fuse gG or gM.
control fuse B or C, and comply with IEC 90947-2. -
BESB 3006652-2023-09.27.fm GB - BESB – Product information
8/64
General Ventilators marked “EC” have a built-in EC control system.
Cables The wiring for control signal inputs must be completely insulated from the supply wirings.
NB Due to EMC requirements the cable between the EC control and the EC motor must not
be elongated.
ESD
The electrician must be ESD protected when
detaching the cover on the EC control
working with the EC control
1.4.1.1 BESB250-4-1EC2, BESB315-4-1EC2, BESB400-4-1EC2 & BESB500-4-1EC2
Cabletype Cables for control signals must be with twisted pair conductors. As a minimum, the cable
type must be CAT5e Ethernet cable.
Diagram
1.4.1 Ventilator with EC control
BESB 3006652-2023-09.27.fm GB - BESB – Product information
9/64
1.4.1.2 DTV160-4-1 & DTV200-4-1
Cable type Cables for control signals must be shielded.
Diagram
Key to diagram
Terminal Signal description Comments
1RS485 + (A)
2RS485 - (B)
3 0 V DC (chassis)
4 10 V DC EFC1P/EFC1P2 panel 5
5 0-10 V DC EFC1P/EFC1P2 panel 4
6 0 V DC (chassis) EFC1P/EFC1P2 panel 3
7
8 Start/stop EFC1P/EFC1P2 panel 2
9
10 0 V DC (chassis)
11 Run NC
12 Run C
13 Run NO
14 Alarm NC
15 Alarm C EFC1P/EFC1P2 panel B
16 Alarm NO EFC1P/EFC1P2 panel A
BESB 3006652-2023-09.27.fm GB - BESB – Product information
10/64
Leakage current The EC control produces a leakage current when running. The leakage current must be
earthed, as there is a risk of the motor becoming live.
A leakage current of up to 150 mA can be generated.
To comply with EN50178, the fan must be suitably earthed.
Earth leak circuit
breakers
If current earth leak circuit breakers are fitted in the installation, they must be of
a type that meets the following requirements:
PFI type B breaker according to EN 61008, that breaks the circuit when a
vagrant current with DC content (pulsating DC) or smooth vagrant current
is registered.
The circuit breakers must be marked with the following symbols:
BESB 3006652-2023-09.27.fm GB - BESB – Product information
11/64
1.4.2 Troubleshooting DV-EC control
DV-EC-control
LED indicator The DV-EC control is equipped with a two-coloured green and red LED indicator
of the different operating modes.
The LED is located on the underside of the control unit next to the cable entry for
the main voltage connection.
Troubleshooting
chart
Steady green when main voltage is connected.
Flashes green when Modbus communication is active.
Steady red for at least one critical alarm.
Flashes red for at least one non-critical alarm.
LED error indicator:
1 flash = Supply problem
3 flashes = Internal DV problem
5 flashes = motor problem
Accessory As an accessory you can buy a handheld terminal for operation and alarm info.
BESB 3006652-2023-09.27.fm GB - BESB – Product information
12/64
Flexible
connections
The ventilator must always be connected to the duct system with FLF, to avoid any
chance of vibrations being transmitted. The spigots on the ventilator are standard-sized
and fitted with rubber seals.
To achieve maximum performance with minimal energy consumption the ventilator
should be connected to the duct system with the specified lengths of duct before and
after the ventilator. The FLF connections must always be fitted as shown.
Sound pressure
level
The ventilator is fitted with sound dampers suited to the requirements of the operating
area. The sound pressure for all types of BESB is less than 70 dB (A). The duct system
is insulated against sound propagation, heat loss, fire and condensation.
No Duct A protective net (accessory) with mesh size of 12 mm must be fitted if the ventilator is
not fitted to a duct. It should be noted that:
such fittings result in a pressure drop in the system
Air volume measurements cannot be measured correctly when there is no duct
fitted on the suction side
1.5 Connecting to duct system
RD11360-01
RD11361-01
BESB 3006652-2023-09.27.fm GB - BESB – Product information
13/64
The box ventilators, aside from model BESB250, have measuring points for determining
air flow. A manometer is connected to the test points and the air flow (qv) can be
calculated by using the formula and diagrams.
Margin of error < ± 8% of actual air flow with the duct system on the suction side is as
shown on the diagrams.
Calculations are based on the following conditions:
Temperature: 20°C
Density: 1.2 kg/m3
Pressure measurement, pm [Pa], at 20°C
1 m3/s = 1000 l/s = 3600 m3/h
1.6 Airflow measurement
BESB315:
BESB400:
BESB500:
qv59 pm
l s =
qv75 pm
l s =
qv87 pm
l s =
BESB 3006652-2023-09.27.fm GB - BESB – Product information
14/64
EXHAUSTO provides a two-year factory warranty on the box ventilator, valid from
invoice date. The motor in an EXHAUSTO box ventilator is fitted with special ball
bearings that are lubricated and sealed, and maintenance-free. Any replacement of
these bearings should be carried out by technicians from EXHAUSTO SERVICE or
similarly qualified professionals.
The ventilator must be cleaned at least once a year. To clean the ventilator:
Switch off the power supply to the
ventilator using the isolation switch.
Open the service door when the fan
has stopped running.
Wash the ventilator housing and the
centrifugal impeller thoroughly with
soap and water. The parts must be
dry and the service door closed
before the ventilator is restarted.
The centrifugal impeller can be
dismounted and cleaned. Measure
the exact position of the impeller on
the axle before removing it. The
factory position of the impeller is
shown on the cabinet behind the
service door. If there are weights on
the centrifugal impeller do not remove
them.
Check that cooling air can move
freely through the motor cover.
Product
description
EXHAUSTO BESB is a an easily serviced radial fan with backward curved blades. The
fan is insulated against fire, noise and heat with 50 mm of mineral wool. The fan impeller
is directly mounted on the motor shaft, thus reducing losses and wear and resulting in
lower repair costs.
Servicing and cleaning are performed by opening the hinged door for access to all parts
in contact with the air. The motor is mounted outside the airstream.
The fan is supplied with mounting rails with vibration dampers. The fan is CE approved
and EMC tested in accordance with the applicable directives.
Materials used Cabinet, fan housing and mounting rails are made of recycleable hot-dip galvanised
steel sheet. Fan impellers are made of recycleable pressure-cast aluminium.
The insulation consists of mineral wool which can be recycled after dismantling the fan.
The gaskets consist of CFC and HCFC free cellular rubber.
The motor consists of aluminium, steel and copper, and in some cases a plastic cooling
jacket. The packaging consists of corrugated cardboard and a wooden disposable
pallet.
1.7 Service and cleaning
1.8 Environmental declaration
BESB 3006652-2023-09.27.fm GB - BESB – Product information
15/64
Materials in %
BESB250EC2 BESB250EC2 BESB250EC2 BESB250EC2 BESB500EC
3-phase
Aluminium 11% 13% 14% 14% 14%
Fe 74% 70% 70% 70% 70%
Copper 1% 1% 1% 2% 2%
Mineral wool 9% 11% 12% 12% 12%
PCB;
electronic
components
3% 3% 2% 1% 2%
Plastic, cellular
rubber
1% 1% 1% 1% 1%
Other 1% 1% 1% < 1% 1%
BESB 3006652-2023-09.27.fm DK - BESB - Produktvejledning
16/64
1. DK - BESB - Produktvejledning
EXHAUSTO boxventilator BESB anvendes til transport af luft i indblæsnings- og
udsugningsanlæg.
Ventilatoren må ikke anvendes til transport af faste partikler, eller hvor
der er risiko for eksplosive gasarter.
Ventilatoren må ikke startes med åben servicelåge.
Beskrivelse BESB findes i 4 størrelser og er en totalisoleret og lyd-svag centrifugalventilator med
bagudbøjede skovle (B-hjul) i støbt aluminium:
• BESB250-4-1EC2
• BESB315-4-1EC2
• BESB400-4-1EC2
• BESB500-4-1EC2
• BESB500-4-3EC
Ventilatoren består indvendigt af et ventilatorhus, som er isoleret, og udvendigt af et
kabinet, begge dele af aluzink.
Hoved-
komponenter
Temperatur medie min.: -12°C max.: +80°C
Temperatur omgivelser, drift min.: -30°C max.: +40°C
1.1 Opbygning
Pos. Part
a Kabinet
b Servicelåge
c Motor
d Centrifugalhjul (B-hjul)
e Ventilatorhus
f Låseskrue (værktøj medleveres)
g Håndtag
h Bæreskinne med svingningsdæmpere
i Selvskærende skrue
j Hængsel
k DV/EC-styring/klemkasse
m Målestudse til luftmængde måling (ikke BESB250)
ab
c
d
e
ih
k
-12°C - +80°C
-30°C - +40°C
+
-
m
g
f
j
RD13284-01
BESB 3006652-2023-09.27.fm DK - BESB - Produktvejledning
17/64
Ventilatoren leveres emballeret og kan transporteres på træpalle. Efter udpakning skal
ventilatoren transporteres og behandles således, at kabinet og studse m.v. ikke
deformeres, da dette kan forårsage berøring imellem roterende dele og heraf følgende
behov for efterjustering/reparation.
Ved transport gennem trange passager ind til opstillingsstedet, er der mulighed for
demontering af servicelågen som vist i afsnit 2.1” Opbygning”.
Bemærk Ventilatoren må ikke løftes i håndtaget på servicelågen.
Vægt
1.3.1 Indendørs placering
Ventilatoren kan indendørs monteres på
forskellige måder.
Ved monteringsmetode B og D skal
servicelågen kunne fastholdes i åben
position ved servicering. Til dette formål
kan leveres et sikkerhedsbeslag incl.
monteringssæt som tilbehør.
Ved intermitterende drift, hvor der er risiko
for kondensvand i motoren, må kun
monteringsmetode A eller B benyttes.
Serviceadgang Ved udvælgelse af den nøjagtige placering
skal der være plads til, at servicelågen kan
åbnes ca. 80° og der skal være adgang til
låseskruerne.
Advarsel Motoren må aldrig placeres lodret under kabinettet og desuden skal det
sikres, at motor og DV/EC-styring ikke tildækkes, da det vil kunne
forårsage overophedning.
1.2 Transport
BESB 250 315 400 500
(kg) 52 57 73 88 91(-3)
1.3 Montage
RD13304-01
D
D
BESB 3006652-2023-09.27.fm DK - BESB - Produktvejledning
18/64
1.3.2 Udendørs placering (OD)
Hvis ventilatoren har typebetegnelsen OD
er det en udendørs variant og kan
anvendes til transport af luft i
temperaturområdet op til 200°C. Desuden
er varianten forsynet med afløb i
monteringsmetode “A”.
Ved udendørs montage skal
monteringsmetode A eller B benyttes.
Monteringsmetode C og D kræver en
specialbygget ventilator - kontakt
EXHAUSTO.
Alle udvendige samlinger samt studse er
fuget for at forhindre vandindtrængning.
Kabinettets materialer opfylder kravene til
klasse C4 iht. DS/EN ISO12 944.2 og er egnet til udendørs placering.
Serviceadgang Ved udvælgelse af den nøjagtige
placering skal der være plads til, at
servicelågen kan åbnes ca. 80° og der
skal være adgang til låseskruerne.
1.3.3 Montage af bæreskinner
Underlaget skal være plant, stabilt og svingningsdødt for at minimere overførslen
af eventuelle svingninger fra ventilatoren. Anvend f.eks. en cementflise oven på
en solid trækonstruktion.
Monter bæreskinnerne på kabinettet med de medleverede skruer. I
monteringsmetode A er kabinettet forboret.
BESB 400 og 500: Når monteringsmetode B vælges til BESB400 og 500, bores
frihuller (Ø16 - Ø20) i kabinettet for møtrikkerne på bæreskinnerne.
Monter bæreskinnerne mens ventilatoren ligger på træpallen af hensyn til
transporten.
Stil ventilatoren løst oven på underlaget. Den skal ikke fastspændes.
A
B
C
D
RD13304-01
D
D
RD13303-01
BESB 3006652-2023-09.27.fm DK - BESB - Produktvejledning
19/64
Generelt
El-installationen skal foretages af autoriseret el-installatør.
Ventilator- og motorspecifikationer fremgår
af de monterede typeskilte.
Max. forsikring = 13 Amp.
Max. kortslutningsstrøm er 10 kA
Ved opstart og indregulering af ventilationsanlægget er det vigtigt at kontrollere
motorens omløbsretning, og at strømforbruget ikke overstiger mærkestrømmen på
typeskiltet, da det vil medføre overbelastning af motoren.
Forsyningsadskiller EXHAUSTO A/S gør opmærksom på, at der i henhold til
Maskindirektivet (bilag 1) skal opsættes en forsyningsadskiller i den
faste installation af ventilatoren.
Forsyningsadskilleren skal...
være aflåselig, eller placeres synligt i nærheden af ventilatoren.
kunne afbryde alle poler fra forsyningsspændingen
- kontaktafstand min. 3 mm i hver pol.
udføres som forsyningsadskiller i hht. IEC 60947-1 eller IEC 60947-3
Forsyningsadskilleren er ikke en del af EXHAUSTO’s leverance.
Lynafledning... ...skal ske i henhold til gældende love og bestemmelser.
1.4 El-tilslutning
RD13301-01
Hvis forsikringen er en ...skal den være med karakteristik
smeltesikring gG eller gM.
automatsikring B eller C, og opfylde IEC 90947-2.
BESB 3006652-2023-09.27.fm DK - BESB - Produktvejledning
20/64
Generelt Alle ventilatorer med typebetegnelsen "EC" er regulerbare via den indbyggede EC-
styring.
Kabler De ledninger, der skal tilsluttes styresignal-indgangene, skal i hele deres længde have
en forstærket isolering i forhold til forsyningledningerne.
Bemærk Pga. EMC-krav må kablet mellem EC-styringen og EC-motoren ikke forlænges.
ESD Elektrikeren skal være ESD-beskyttet:
når låget på EC-styringen demonteres
1.4.1.1 BESB250-4-1EC2, BESB315-4-1EC2, BESB400-4-1EC2 & BESB500-4-1EC2
Kabeltype Kabler til styresignaler skal være med parsnoede ledere. Kabeltypen skal minimum
være CAT5e Ethernet kabel.
Diagram
1.4.1 Ventilator med EC-styring
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

EXHAUSTO BESB Version 2 Bruksanvisningar

Typ
Bruksanvisningar