Warning!
High voltage. Risk of electric
shock. The installation should
only be carried out by an
authorised electrician.
1. Press and hold down any of the two buttons until
numeric digital display flashes, then release the
button.
2. Click any of the two buttons once to select a digit,
click again to change the digit until the desired
DALI address appears. Click first button to set
“tens” position and second button to set “units”
position. The address can be set from 00~63.
3. Then press and hold down any of the 2 buttons
until the numeric digital display stops flashing to
confirm the setting.
Note! DALI address can be manually assigned from 00-63-
FF. By factory defaults, no DALI address is assigned for the
driver, and the display shows . Setting DALI address
as will reset the dimmer to factory defaults.
1. Press and hold down both of the two buttons until
numeric digital display flashes, then release the
button.
2. Click first button to select “1A”, “2A”, “3A” or “4A”
which means 1/2/3/4 DALI addresses
3. Then press and hold down any of the 2 buttons
until the numeric digital display stops flashing to
confirm the setting.
For example, when we set DALI address to 00:
• When select 1A, all 4 channels load will be the
same address 00, and controlled simultaneously.
• When select 2A, channel L1&L3 will be same ad-
dress 00, channel 2&4 will be same address 01.
• When select 3A, channel L1&L4 will be address 00,
channel L2 will be address 01, channel L3 will be
address 02.
• When select 4A, channel L1 will be address 00,
channel L2 will be address 01, channel L3 will be
address 02, channel L4 will be address 03.
Note! The channels with same the address will be
controlled simultaneously, the channels with different
addresses will be controlled separately.
Set DALI Address Quantity
DD1600 is a 4-channel DALI phase dimmer with trailing edge dimming. Suppots
resistive loads and capacitive loads. With DALI signal input, DALI address can be
set with buttons and displayed on the digital display. DALI address quantity can
be set as 1/2/3/4 to control the 4 channels load simultaneously or separately.
Operation
Set DALI address manually via buttons The factory dimming range is 1%~100%, but the 1% can
be can be re-set as below:
Operate the DALI master to dim the load of L1 to a bright-
ness you want, then press and hold down the Min. set
button until the light flashes, which means the minimum
point is set at this brightness now. You can not dim lower
than this brightness point. The minimum point will be
covered by repeating doing that.
How to reset it to factory defaults: dim up the Load of L1
to 100% , then press and hold Min. set button until the the
load of L1 flashes.
Note! The dimming range of this dimmer is 1%-100%, but
some load types may flicker when dimmed to 1%, thus a
minimum brightness shall be set higher than 1% to avoid
flickering during dimming process.
Whatever the DALI address quantity is set as: 1A, 2A, 3A,
4A, the minimum brightness shall be set or reset only by
adjusting Load L1 output brightness and pressing Min. set
button. Once the minimum brightness is set, all 4 chan-
nels load can not be dimmed below this value.
Set the minimum dimming brightness point
DALI address can also be assigned by DALI Master
controller automatically, please refer to user manuals of
compatible DALI Masters for specific operations.
Note! The digital display will show AU when the DALI
master is assigning addresses.
Set DALI Address Assigned by DALI Masters
EN Installation manual DD1600
DD1600
V-40D1600-021
See figure 1.
100-240VAC
4x(100-240)VAC
4×1.5A
4×400W @ 230V,
4×200W @ 110V
DALI phase dimmer,
trailing edge dimming
1-100%
<2mA
White
PC
145.5×90×66.5mm
Dimmable LED lamps,
dimmable LED driver,
traditional incandescent
and halogen lights
IP20
CE
Label
Item number
Power
Input voltage
Output voltage
Max. load current
Max. load power
Function
Dimming range
DALI consumption
Colour
Casing material
Size (LxWxH)
Area of use
Casing classification
Cetifications
Technical data
Compatible Load Types (figure 1)
Load Type Maximum Load Remarks
Dimmable LED lamps 1*200W @ 110V, 1*400W @ 230V
2*150W @ 110V, 2*300W @ 230V
3*125W @ 110V, 3*250W @ 230V
4*100W @ 110V, 4*200W @ 230V
Due to variety of LED lamp
designs, maximum number of
LED lamps per channel is futher
dependent on power factor result
when connected to dimmer.
Dimmable LED drivers 1*200W @ 110V, 1*400W @ 230V
2*150W @ 110V, 2*300W @ 230V
3*125W @ 110V, 3*250W @ 230V
4*100W @ 110V, 4*200W @ 230V
Maximum permitted number of
drivers per channel is 200W/400W
divided by driver nameplate power
rating.
Incandescent lighting and
Halogen 240V lamps 1*400W @ 110V, 1*800W @ 230V
2*300W @ 110V, 2*600W @ 230V
3*250W @ 110V, 3*500W @ 230V
4*200W @ 110V, 4*400W @ 230V
Low voltage halogen
lighting with electronic
transformers
1*200W @ 110V, 1*400W @ 230V
2*150W @ 110V, 2*300W @ 230V
3*125W @ 110V, 3*250W @ 230V
4*100W @ 110V, 4*200W @ 230V
100-240VAC
power input.
4 channels
load output.
Digital
display.
Manual set
buttons.
Min. set
button to set
minimum
dimming
level.
2 groups DALI
signals input & output.
Besöks-/postadress/Visiting:
Hilm Anderssons gt 15
421 31 Västr Frölund
Telefon/Phone:
+46 (0)31-23 56 00
E-post/E-mail:
info@vadsbo.net
order@vadsbo.net
Hemsida/Website/Facebook:
www.vadsbo.net
facebook.com/Vadsbo
Reverse-phase control (trailing edge)
Voltage
-
+
Dimensions
145.5
66.5
90
2022-04-04 DD1600
Installationsmanual Version 4