www.sentera.eu
MIW-AH2C1-6-SV-000 - 15 / 06 / 2022 10 - 11
tillbaka till
innehållsförteckningen
MODBUS REGISTERLISTA
Input registers
Data type Description Data Values
1Actual Temperature Level signed int Actual temperature. 200 = 20.0°C
2Current Output Duty Cycle signed int Current output in % 0-100 100 = 100%
3Selected Setpoint signed int Current setpoint in °C 50-300 300 = 30.0°C, 5—30°C
4–9 Reserved. Return 0.
10 Setpoint Source Selected
(Ext.SP / Int.SP) unsigned int Shows which setpoint is used - external by analogue input or internal
by trimmer or Modbus register 0,1 0 - External; 1 - Internal
11 Working Mode (Slave/Master) unsigned int Shows how the controller is working: as a Master providing analogue
output for a Slave device or as a Slave when the output in % repeats
the analogue input 0,1 0 - Slave; 1 - Master
12 Day / Night Mode unsigned int Shows which setpoint is active: selected by NO switch 0,1 0 - Day; 1 - Night
13 Remote Off Contact unsigned int Shows if the device is in remote off: selected by NC switch 0,1 0 - On, 1 = Standby.
14 Control Board Problem Shows if there is problem with the communication with the control
board 0,1 0 - OK,1 - Problem.
15–18 Reserved. Return 0.
Holding registers
Data type Description Data Values
1Device Slave Address unsigned int Device address. 1—247, default:1
2Baud rate unsigned int Modbus communication baud rate. 1—4, default: 2 1 = 9600, 2 = 19200, 3 = 38400,
4 = 57600
3Parity mode unsigned int Parity check mode. 0—2, default:1 0=8N1, 1=8E1, 2=8O1
4Device Type unsigned int Device Type: Read Only 6000, 6001 6000 = AH2C1-6, 6001 = AH2C1-
6-500,
5HW Version unsigned int Hardware Version. Read only XX.XX 0x0110 = HW version 1.10
6SW version unsigned int Software Version. Read only XX.XX 0x0120 = SW version 1.20
7Operating mode unsigned int Enables the Modbus control and disables the jumpers and trimmers. 0-1 0 = Standalone mode, 1 = Modbus
mode.
8Output Override unsigned int Enables the direct control over the outputs. Always settable. Active
only if holding register 7 is set to 1. 0-1 0 = Disabled, 1 = Enabled, default: 0.
9–10 Reserved. Return 0.
11 Day Setpoint Selection unsigned int Day setpoint 50—300, Default
250 300 = 30.0°C, 5—30°C
12 Night Setpoint Selection unsigned int Day setpoint 50—300, Default
180 300 = 30.0°C, 5—30°C
13 Working Mode unsigned int Slave or master in Modbus mode 0—1 Default 1; 0 - Slave, 1 - Master,
14 Setpoint Source Selection unsigned int External or Internal (Modbus) setpoint 0—1 Default 1; 0 = External setpoint, 1 = Internal
setpoint
15 Triac Control PWM Output Period unsigned int PWM period time 1—60 default 30. 60 = 60sec.
16 Calibration at 10°C unsigned int Register containing the calibration value for 10°C. Write 1 to
perform calibration. 0—1023; Default
210
17 Calibration at 30°C unsigned int Register containing the calibration value for 30°C. Write 1 to
perform calibration. 0—1023, Default
490
18 Disable Remote Off. unsigned int Disables/enables the Remote Off Contact (CC) 0, 1, default:1. 0 - Disabled, 1 - Enabled.
19–20 Reserved. Return 0.
21 Override Output Value signed int Override output value in %(only active if registers 7 and 8 are set) 0—100; default 0. 100 = 100%
22–30 Reserved. Return 0.
For more information about Modbus over serial line, please visit: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
Enhetens parametrar kan övervakas / konfigureras via den kostnadsfria 3SModbus-
programvaruplattformen. Du kan ladda ner den från Senteras webbplats. Det finns
två typer av register i en Modbus Registerlista:
Input register (se tabell Input register ovan)
Input register är skrivskyddade. All data kan läsas med kommandot "Läs Input
register”. Tabellen Input register visar den returnerade datatypen och hur den ska
tolkas.
Holding register (se tabell Holding register ovan)
Dessa register är läs- / skrivregister och de kan hanteras via kommandona "Läs
Holding register”, "Skriv enkel register" och "Skriv flera register". De register som
inte används är skrivskyddade och därför returnerar skrivning i dessa register varken
ett Modbus-felundantag eller gör det några ändringar.
AH2C1-6 ELEKTRONISK