Sentera Controls MVSS1-15CDM Mounting Instruction

Typ
Mounting Instruction
Installations- och bruksanvisning
MVSS ELEKTRONISK
FLÄKTHASTIGHETSREGULATOR MED TK
FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 2 - 16
Innehållsförteckning
KERHET OCH FÖRSIKTIGHETSÅTGÄRDER 3
PRODUKTBESKRIVNING 4
ARTIKELKODER 4
AVSETT ANVÄNDNINGSOMRÅDE 4
TEKNISKA DATA 4
STANDARDER 5
LEDNINGAR OCH FÖRBINDELSER 5
DRIFTSDIAGRAM 6
INSTALLATIONSANVISNINGAR I STEG 8
VERIFIERING AV INSTALLATION 10
BRUKSANVISNINGAR 11
MODBUS REGISTERLISTA 12
TRANSPORT OCH LAGRING 16
GARANTI OCH BEGRÄNSNINGAR 16
UNDERHÅLL 16
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 3 - 16
tillbaka till innehållsförteckningen
SÄKERHET OCH FÖRSIKTIGHETSÅTGÄRDER
Läs all information, datablad, installations- och bruksanvisning och betrakta
anslutningsdiagrammet innan du arbetar med produkten. För personlig och
utrustningens säkerhet och för optimal produktprestanda, se till att du förstår
innehållet innan du installerar, använder eller underhåller produkten.
Av säkerhets- och godkännandeskäl (CE) är inga obehöriga omvandlingar och/eller
modifikationer av produkten tillåtna.
Produkten får inte utsättas för onormala förhållanden såsom extrema
temperaturer, direkt solljus eller vibrationer. Långvårig exponering för kemiska
ångor i hög koncentration kan påverka produktens prestanda. Håll arbetsplatsen
så torr som möjligt, se upp för kondens.
Alla installationer ska följa lokala hälso- och säkerhetsföreskrifter, lokala elektriska
standarder och godkända koder. Produkten får bara installeras av en ingenjör
eller tekniker som har expertkunskaper om produkten och om de nödvändiga
försiktighetsåtgärderna.
Undvik kontakter med strömförande elektriska delar. Koppla alltid ur strömkällan
innan du ansluter elkablarna, utför service eller reparerar produkten.
Kontrollera att du väljer rätt strömförsörjning till produkten och att du använder
kablar med rätt storlek och egenskaper. Se till att alla skruvar och muttrar är väl
åtdragna och att eventuella säkringar sitter på plats.
Utrustningen och förpackningen kan återvinnas och ska bortskaffas i enlighet med
lokala och nationella lagar och bestämmelser.
Om du har ytterligare frågor, kontakta din tekniska support eller rådfråga en
expert.
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 4 - 16
tillbaka till innehållsförteckningen
PRODUKTBESKRIVNING
MVSS-serien styr hastigheten på enfas spänningsstyrbara elmotorer
(230 VAC / 50—60 Hz) baserat på en standard styrsignal. De är utrustade med
Modbus RTU-kommunikation, en larmreläutgång och termiska kontakter för att
ge överhettningsskydd för motorer med brytkontakter. De erbjuder ett stort antal
funktioner: ärrstyrningsalternativ, justerbar avstängningsnivå, inställningar för min.
och max. utspänning och tidsbegränsad motordrift som initieras av en logik- eller
omkopplingssignal.
ARTIKELKODER
Kod Nominell ström, [A] Säkringsklass
Säkring 1 Säkring 2
MVSS1-15CDM 1,5
F 0,315 A H 250 V
(5*20 mm)
F 3,15 A H 250 V
(5*20 mm)
MVSS1-30CDM 3,0 F 5,0 A H 250 V
(5*20 mm)
MVSS1-60CDM 6,0 F 10,0 A H 250 V
(5*20 mm)
MVSS1100CDM 10,0 F 16,0 A H 250 V
(6,3*32 mm)
AVSETT ANNDNINGSOMRÅDE
Fläkthastighetsreglering i ventilationssystem
Applikationer där Modbus -kommunikation eller en timerfunktion behövs
Endast för inomhusbruk
TEKNISKA DATA
Strömförrjning: 230 VAC ±10 %/5060 Hz
Analog ingång:
spänning: 0–10 VDC
ström: 0—20 mA
Analoga ingångslägen: stigande eller fallande
Analog ingångsfunktion: Normalt läge / Logik-läge
Fjärrkontrollingång: normal eller timerfunktion
Reglerad utgång: 30100 % Us
Max. belastning: beror på versionen (se tabellen ovan)
Oreglerad utgång, L1: 230 VAC / 5060 Hz/max. 2 A
Larmutgång (230 VAC / 1 A)
Inställning av minsta utspänning, Umin: 3070 % Us (69—161 VAC), valbar via
trimmer eller via Modbus
Inställning av maximal utspänning, Umax: 75100 % Us (173230 VAC), valbar
via trimmer eller via Modbus
O-nivå, justerbar via trimmer eller via Modbus:
04 VDC/08 mA för stigande läge
106 VDC/2012 mA för fallande läge
Direktstart eller mjukstart
Utgång för lågspänningsförsörjning: + 12 VDC / 1 mA för extern potentiometer
Modbus kommunikation
Driftsindikering:
kontinuerlig grön: normal drift
blinkande grön: vänteläge
Överspännings- och överströmsskydd
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 5 - 16
tillbaka till innehållsförteckningen
Termiska ingångar för skydd mot överhettning av motorn
Kapsling:
Gränssnittsmodul för DIN-skena: polyamid - PA UL94V0; grön (RAL 6017)
Lock: plexiglas, transparent
Kapslingsklass: IP20 (enligt EN60529)
Omgivningsförhållanden vid drift:
temperatur: -20—40 °C
relativ luftfuktighet: < 80 % rH (icke-kondenserande)
Förvaringstemperatur: -40—50 °C
STANDARDER
Lågspänningsdirektiv 2014/35/EU
EMC-direktiv 2014/30/EU
RoHs-direktiv 2011/65/EU
LEDNINGAR OCH FÖRBINDELSER
L Matningssnning, 230 VAC ± 10 % / 5060 Hz
NNeutralledare
L1 Oreglerad utgång (230 VAC / max. 2 A)
U1, U2 Reglerad utgång till motor
TK, TK Termokontakter
NNeutralledare
AL Larmutgång (230 VAC / 1 A)
SW Fjärr- / timeromkopplare
+V Uteekt + 12 VDC/1 mA
Ai
Analog ingång:
(010 VDC/0—20 mA) or (100 VDC/200 mA)
Logik ingång (timerfunktionalitet):
(minst 2,5 VDC och > 30 ms)
GND Jord
A Modbus RTU (RS485), signal A
/B Modbus RTU (RS485), signal /B
Anslutning Kabeltvärsnitt: max 2,5mm2
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 6 - 16
tillbaka till innehållsförteckningen
DRIFTSDIAGRAM
Normalt / Fjärrstyrt driftsläge
Stigande ingångsläge Fallande ingångsläge
Avstängd nivå inaktiverad
U
out
,
[%]
10 VDC
20 mA
Umax
Umin
0
Ai ,
[VDC]/[mA]
100
75
70
30
Umax
område
Umin
område
U
out
,
[%]
10 VDC
20 mA
Umax
Umin
0
Ai ,
[VDC]/[mA]
100
75
70
30
Umax
område
Umin
område
Beräkningsformel
för stigande läge
Uout=Umin+ Aimax
Ai
(Umax-Umin)
Beräkningsformel för
fallande läge
Uout=Umax- Aimax
Ai
(Umax-Umin)
Umax
Umin
0
,Ai
[VDC]
/
[mA]
4 VDC
8 mA
U,
[%]out
100
75
70
30
10 VDC
20 mA
Umax
område
Umin
område
Område
Off-nivå
Off-nivå
område
Umax
Umin
0
,Ai
[VDC] /
[mA]
10 VDC
20 mA
6 VDC
12 mA
U, [%]out
100
75
70
30
Umax
område
Umin
område
O-nivå
Avstängd nivå aktiverad
Beräkningsformel
för stigande läge
Uout=Umax+ Aimax-Off level
Ai-Off level (Umax-Umin)
Beräkningsformel för
fallande läge
Uout=Umax- Aimax-Off level
Ai-Off level (Umax-Umin)
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 mA
Uout, [%]
100
75
70
30
0 VDC / 0 m
Umax
område
Umin
område
Direktstart varaktighet
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 m
A
Uout, [%]
100
75
70
30
0 VDC / 0 mA
Umax
område
Umin
område
Direktstart varaktighet
Direktstart aktiverad
t [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
10 VDC /
20 mA
Ai,
[VDC]/
[mA]
Umax
område
Umin
område
Mjukstart varaktighet
Off-nivå
t [s]
Umax
Umin
Uout, [%]
100
75
70
30
10 VDC /
20 mA
0 VDC /
0 mA
Ai,
[VDC]/
[mA]
Umax
område
Umin
område
Mjukstart varaktighet
Off-nivå
Mjukstart aktiverad
O-nivå
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 7 - 16
tillbaka till innehållsförteckningen
Stigande ingångsläge Fallande ingångsläge
Mjukstart och avstängt läge
t [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
10 VDC /
20 mA
Ai,
[VDC]/
[mA]
Umax
område
Umin
område
Mjukstart varaktighet
Off-nivå
t [s]
Umax
Umin
Uout, [%]
100
75
70
30
10 VDC /
20 mA
0 VDC /
0 mA
Ai,
[VDC]/
[mA]
Umax
område
Umin
område
Mjukstart varaktighet
Off-nivå
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 mA
Uout, [%]
100
75
70
30
0 VDC / 0 m
A
Umax
område
Umin
område
Direktstart varaktighet
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 m
A
Uout, [%]
100
75
70
30
0 VDC / 0 mA
Umax
område
Umin
område
Direktstart varaktighet
Direktstart & avstängt läge
Timer modus Logik modus
0
t, [s]
5 VDC
2,5 VDC
Fjärr
kontroll,
[VDC]
Stand-by Drift
Spänning
amplitud
område
Brytare kontrollsignal
t [s]
0
U
out, [%]
100
75
Umax
område
Direktstart
varaktighet Drifttimer Regulatorn är
avstängd
Direktstart aktiverad
Mjukstart aktiverad
t
t
t
t
SW
Holding
register
18
Holding
register
21
Mjukstart
varaktighet Mjukstart
varaktighet
Start
Utgång
Umax
Timer
Mjukstart
Stopp
Start
Stopp
Drift
timer
Driftstid
Holding
register
18
AV AV
Brytare kontrollsignal
t
t
t
t
Ai >2,4 VDC
PÅ PÅ
Holding
register
18
Holding
register
21
Holding
register
21
Mjukstart
varaktighet Mjukstart
varaktighet
Start
Utgång
Umax
Timer
Mjukstart
Start Stopp
Drift
timer Drift
timer
Holding
register
18
AV AV
Ai kontrollsignal
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 8 - 16
tillbaka till innehållsförteckningen
INSTALLATIONSANVISNINGAR I STEG
Innan du börjar montera MVSS-styrenheten, läs noggrant "Säkerhet och
försiktighetsåtgärder". Fortsätt sedan med följande steg:
1. Stäng av strömförsörjningen.
2. Ta bort det genomskinliga locket på DIN-kapslingen.
3. Skruva loss sidorna på DIN-skenmodulen. Montera modulen på en standard DIN-
skena. Fäst i önskat läge på skenan genom att montera höljets sidor. Tänk på rätt
monteringsmått (Fig. 1) och monteringsposition (Fig. 2).
Fig. 1 Monteringsmått
MVSS1-60CDM
MVSS -1100CDM
MVSS1-15CDM
MVSS1-30CDM
H
L
W
MVSS1-15CDM, MVSS1-30CDM
Höjd [mm] Längd [mm] Bredd [mm]
96 127 112
MVSS1-60CDM, MVSS1100CDM
96 127 128
Fig. 2 Monteringsposition
DIN-skena
4. Gör anslutningen enligt kopplingsschemat (Fig. 3) och enligt informationen i
avsnitt "Ledningar och förbindelser".
5. Anslut L1-utgången för en 3-trådig anslutning, styrd ventil osv. (om nödvändigt).
Se Fig. 3b 3-tråds motoranslutning.
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 9 - 16
tillbaka till innehållsförteckningen
Fig. 3 Kopplingsschema
Strömförsörjning
230 VAC ,
5060 Hz
Termokontakt
Larmutgång
Brytare för
ärrkontroll
Modbus RTU
Analog ingång
010 VDC / 0—20 mA
Matningsutgång
+12 VDC / 1 mA
L
N
PE
Oreglerad
utgång
230 VAC / max. 2 A.
M
3a 2-tråds motoranslutning
Strömförsörjning
230 VAC ,
5060 Hz
Termokontakt
Larmutgång
Brytare för
ärrkontroll
Modbus RTU
Analog ingång
010 VDC / 0—20 mA
Matningsutgång
+12 VDC / 1 mA
L
N
PE M
3b 3-tråds motoranslutning
6. Välj önskad analog ingångstyp och läge, startläge och o-nivå med DIP-
omkopplaren på kretskortet. (Se Fig. 4 Inställningar för DIP-omkopplare.)
Fig. 4 Inställningar för DIP-omkopplare
Välja stigande/fallande läge
(DIP-switch, position 1)
1 2 3 4
På – Fallande modus:
10—0 VDC/200 mA
Av – Stigande modus:
0—10 VDC/0—20 mA
Välja O-nivå
(DIP-switch, position 2)
1 2 3 4
På – aktiverad
Av – inaktiverad
Välja direktstart/mjukstart
(DIP-switch, position 3)
1 2 3 4
På – Direktstart
Av – Mjukstart
Välja ingångsmodus
(DIP-switch, position 4)
1 2 3 4
PÅ - Stmge
(0–20 mA)
AV - Spänningsläge
(0–10 VDC )
7. Kontrollera om enheten står i böjran eller i slutet av nätverket (se Exempel 1 och
Exempel 2). Om den gör det, använd NBT-bygeln. Om den inte gör det, lämna
bygeln frånkopplad (se Fig. 5).
Exempel 1 Exempel 2
Fig. 5 Bygel för
Network Bus
Terminator
RX
ТX
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 10 - 16
tillbaka till innehållsförteckningen
VARNING Om en AC-taggregat används med någon av enheterna i ett Modbus-
nätverk ska GND-terminalen inte anslutas till andra enheter i nätverket eller
via CNVT-USB-RS485-omvandlaren. Detta kan orsaka permanenta skador på
kommunikationshalvledare och / eller datorn.
8. Justera maxhastighet via trimmern (om det behövs). Standardinställningen är Us
(230 VAC). Se Fig. 6 Trimmer för maxhastighet.
9. Justera minsta hastighet via trimmern (om det behövs). Standardinställningen är
30 % Us (69 VAC). Se Fig. 7 Trimmer för minsta hastighet.
10. Justera off level-värdet via trimmern (om det behövs). Standardinställningen är
0 VAC. Se Fig. 8 Trimmer för Off-nivå.
Fig. 6 Trimmer för maxhastighet Fig. 7 Trimmer för minsta hastighet Fig. 8 Trimmer för O-nivå
11. Stäng höljet och säkra det genomskinliga locket.
12. Slå på strömförsörjningen.
13. Anpassa fabriksinställningarna till de önskade via programvaran 3SModbus eller
Sensistant (vid behov). För fabriksinställningarna, se Tabell Modbus registerlista.
VERIFIERING AV INSTALLATION
Följ instruktionerna nedan:
1. Slå på strömförsörjningen.
2. Ställ in NBT-bygeln, DIP-omkopplaren, trimmern för min. och max. hastighet och
trimmer för OFF-nivå till de önskade positioner / värden. Fabriksinställningarna
är följande:
NBT-bygeln är frånkopplad
Stigande läge: 010 VDC / 0—20 mA
O-läge - AV;
Direktstart inaktiverad;
Inspänningsläge (0—10 VDC);
Minsta inställning för min. hastighetstrimmer;
Maxinställning för max. hastighetstrimmer;
Min. inställning för trimmern för o-nivå.
3. Ställ in den analoga ingångssignalen på maxvärdet 10 VDC eller 20 mA.
4. Den anslutna motorn körs med maximal hastighet eller lägsta hastighet beroende
på det analoga ingångsläget (stigande / fallande).
5. Om OFF-nivå är aktiverad och fallande analogt ingångsläge väljs slutar motorn
att gå.
6. Ställ in den analoga ingångssignalen på maxvärdet 0 VDC eller 0 mA.
7. Den anslutna fläkten körs med lägsta hastighet eller maximal hastighet beroende
på analogt ingångsläge (stigande / fallande).
8. Om OFF-nivån är aktiverad och stigande analogt ingångsläge väljs slutar motorn
att gå.
9. Om O-nivå är aktiverad och insignalen är lika med värdet för O-nivå, kommer
motorhastigheten att vara lägsta hastighet i stigande läge eller maximal
hastighet i fallande läge.
10. Om styrenheten inte fungerar enligt anvisningarna ovan måste
kabelanslutningarna och inställningarna kontrolleras.
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 11 - 16
tillbaka till innehållsförteckningen
11. Kontrollera om båda lysdioderna (Fig. 9) blinkar när du har slagit på enheten.
Om de gör det har din enhet upptäckt Modbus -tverk. Om de inte gör det
kontrollera anslutningarna igen.
Fig. 9 Indikation för uppckt av kommunikation
VARNING Lysdiodernas status kan endast kontrolleras när enheten är strömsatt. Vidta
relevanta säkerhetsåtgärder.
BRUKSANVISNINGAR
DRIFTLÄGEN
I Modbus-läge styr du parametrarna: Umax, Umin, Direktstart / Mjukstart, Off-ni
aktiverad/inaktiverad och off-nivå värde via Modbus register.
I fristående läge styr du parametrarna: Umax, Umin, Direktstart/Mjukstart, off-nivå
aktiverad/inaktiverad och off-nivå värde med hjälp av hårdvaruinställningarna (DIP-
switch, trimmers, byglar).
Normal läge: Om Off-nivån är inaktiverad utförs mjukstart/ direktstart endast en
gång - efter att styrenheten har försetts med ström; i annat fall utförs mjukstart/
direktstart varje gång styrenheten slås på.
När Timer-läget är valt tar regulatorn emot en pulskontrollsignal från
ärrkontrollbrytaren. När logik-läget är valt, tar styrenheten emot en pulsstyrsignal
från Ai-ingången.
I båda lägena (Timer-läge och Logik-läge) ska pulsbredden vara mer än 30 ms
annars filtreras signalen.
LED DRIFTSINDIKATION
När den gröna lysdioden (se Fig. 10) lyser fungerar styrenheten i normalt läge. När
den blinkar:
fungerar styrenheten i ärrstyrningsläge eller
är OFF-nivån aktiverad och ligger den analoga insignalen under OFF-nivåvärdet.
Fig. 10 Driftsindikation
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 12 - 16
tillbaka till innehållsförteckningen
MODBUS REGISTERLISTA
INPUT REGISTERS
Data type Description Data Values
1Analog input level unsigned int. Analog input value depending on the selected analog input
type. 0—100
0 =
100 =
0 =
100 =
0 VDC
10,0 VDC
or
0 mA
20,0 mA
2Current output
voltage unsigned int. Actual output voltage 0,
30—100
0 =
30 =
100 =
0 % Us
30 % Us
100 % Us
3Analog input type unsigned int. Type of the selected analog input 0—1 0 =
1 =
0—20 m A
0—10 VDC
4
Ascending/
descending input
mode
unsigned int. Ascending or descending analog input mode depending on
the selected analog input type. 0—1
0 =
1 =
0 =
1 =
100 VDC
0—10 VDC
or
200 mA
0—20 mA
5Maximum output
voltage unsigned int. Maximum output voltage 75—100 75 =
100 =
75 % Us
100 % Us
6Minimum output
voltage unsigned int. Minimum output voltage 30—70 30 =
70 =
30 % Us
70 % Us
7 Enable off level unsigned int. Enables off level 0—1 0 =
1 =
Disabled
Enabled
8Off level value unsigned int. Off level value depending on the selected analog input type
and ascending / descending analog input mode.
0 — 40
60—100
Ascending mode:
0 =
400 =
0 =
200 =
Voltage
0 VDC
4,0 VDC
Current
0 mA
8,0 mA
Descending mode:
100 =
60 =
100 =
60 =
Voltage
10,0 VDC
6,0 VDC
Current
20,0 mA
12, 0 m A
9Kick start/soft
start unsigned int. Selects kick start or soft start 0—1 0 =
1 =
Soft start
Kick start
10 Remote control
input unsigned int. Remote control input 0—1 0 =
1 =
Disabled
Enabled
12 L1 control unsigned int. L1 control 0—1 0 =
1 =
Off
On
13 Alarm LED unsigned int. Alarm LED 0—1 0 =
1 =
Off
On
14 ON/Stand-by LED unsigned int. ON/Stand-by LED 0—2
0 =
1 =
2 =
Off
On
Stand-by
15-20 Reserved, returns 0
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 13 - 16
tillbaka till innehållsförteckningen
HOLDING REGISTER
Datatyp Beskrivning Data Standard Värden
1Enhetens slav adress osignerat
heltal Enhetens Modbus adress 1—247 1
2Baud-nivå Modbus osignerat
heltal Baud-nivå Modbus kommunikation 1—4 2
1 =
2 =
3 =
4 =
9.600
19.200
38.400
57.600
3Modbus paritet osignerat
heltal Paritets kontrolläge 0—2 10 =
1 =
2 =
8N1
8E1
8O1
4 Typ av enhet osignerat
heltal Typ av enhet (skrivskyddad) MVSS-CDM =
3009
5HW version osignerat
heltal Hardware version of the device (Read only) XXXX 0 x 0300 = HW version 3.00
6FW version osignerat
heltal Enhetens firmwareversion (skrivskyddad) XXXX 0 x 0140 = FW version 1.40
7Driftsläge osignerat
heltal Aktiverar Modbus-kontroll och inaktiverar DIP-
omkopplaren och trimmarna 0—1 00 =
1 = Fristående läge
Modbus-läge
8Åsidottning av
utdata osignerat
heltal
Aktiverar direkt kontroll över utdata. Alltid
settable. Aktiv endast om holding register 7 är
inställt på 1. 0—1 00 =
1 = Inaktiverat
Aktiverat
9-10 Reserverad, returnerar 0
11 Analog ingångstyp osignerat
heltal
Väljer enhetens analoga ingångstyp. Alltid
settable. Aktiv endast om holding register 7 är
inställt på 1. 0—1 10 =
1 = 0–20 mA
0–10 VDC
12 Stigande / fallande
analogt ingångsläge osignerat
heltal
Stigande / fallande analogt ingångsläge. Beror
på den valda analoga inngstypen. Alltid
settable. Aktiv endast om holding register 7 är
inställt på 1.
0—1 1
0 =
1 =
0 =
1 =
100 VDC
010 VDC
eller
200 mA
0–20 mA
13 Maximal utspänning osignerat
heltal
Maximal inställbar utspänning. Alltid settable.
Aktiv endast om holding register 7 är inställt
på 1. 75—100 100 75 =
100 = 75% Us
100% Us
14 Minsta utspänning osignerat
heltal
Minsta inställbara utspänning. Alltid settable.
Aktiv endast om holding register 7 är inställt
på 1. 30—70 30 30 =
70 = 30% Us
70 % Us
15 Aktivera off level osignerat
heltal Aktiverar off level. Alltid settable. Aktiv endast
om holding register 7 är inställt på 1. 0—1 00 =
1 = Inaktiverat
Aktiverat
16 Off level value osignerat
heltal
Off level value Beror på den valda analoga
ingångstypen och stigande / fallande analogt
ingångsläge. Alltid settable. Aktiv endast om
holding register 7 är inställt på 1.
610
60—100 0
Stigande läge:
0 =
40 =
0 =
40 =
Spänning
0 VDC
4,0 VDC
Ström
0 mA
8,0 mA
Fallande läge:
100 =
60 =
100 =
60 =
Spänning
10,0 VDC
6,0 VDC
Ström
20,0 mA
12,0 mA
17 Direktstart /
mjukstart osignerat
heltal
Väljer kickstart eller mjukstart. Alltid settable.
Aktiv endast om holding register 7 är inställt på
1. 0—1 10 =
1 = Mjukstart
Direktstart
18 Direktstart /
mjukstart varaktighet osignerat
heltal
Ställer in varaktighetstiden. Alltid settable.
Aktiv endast om holding register 7 är inställt
på 1. 610 10 0 =
60 = 0 s
60 s
19 Fjärrkontrollens
funktionalitet osignerat
heltal
Ställer in ärrkontrollens ingångsläge. Beror på
det valda kickstart- eller mjukstartsläget. Alltid
settable. Aktiv endast om holding register 7 är
inställt på 1.
0—1 00 =
1 = Normalt läge
Timer modus
20 Analog
ingångsfunktionalitet osignerat
heltal
Ställer in den analoga ingångsfunktionen.
Beror på vald kickstart eller mjukstart. Alltid
settable. Aktiv endast om holding register 7 är
inställt på 1.
0—1 00 =
1 = Normalt läge
Logik modus
21 Driftstimer osignerat
heltal
Ställer in enhetens driftstid när timerläge med
ärrkontrollingång eller logikläge med den
analoga ingången är valt. Driftstiden är utöver
start- / mjukstartstiderna.Alltid settable. Aktiv
endast om innehavsregister 7 och 19 eller / och
20 är inställda på 1.
0—200 60 0 =
200 = 0 s
200 s
22-30 Reserverad, returnerar 0
31 Åsidosättningsvärde
för utdata osignerat
heltal
Åsidosätt värdet för den analoga utgången.
Alltid settable. Aktiv endast om holding register
8 är inställt på 1.
0,
30—100 00 =
30 =
100 =
0% Us
30% Us
100% Us
32-40 Reserverad, returnerar 0
Om du vill veta mer om Modbus över seriell linje, besök:
INPUT REGISTER (se tabell 1 Modbus registerlista)
Input register är skrivskyddade. Tabell 1 visar hur uppgifterna är organiserade i Input
registren. De uppmätta uppgifterna börjar från adress 1 och slutar med adress 14.
Övriga input register används inte. När de adresseras, returnerar de 0.
All data kan läsas med kommandot "Läsa Input Register". Tabell 1 visar vilken typ
av data som returneras för varje register och hur den ska tolkas. Till exempel: "300"
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 14 - 16
tillbaka till innehållsförteckningen
i input register 1 innebär att den uppmätta analoga insignalen är 3,0 VDC (eller
6,0 mA), "50" i input register 2 innebär att utspänningen är 50 % Us (115 VAC).
Input register 1 visar det aktuella värdet av den uppmätta analoga insignalen. Detta
värde beror på den valda analoga ingångstypen. När spänningsläge väljs varierar
värdena mellan 0—1.000 (0—10,0 VDC). När strömläge väljs varierar värdena mellan
0—1.000 (0—20,0 mA).
Input register 2 visar det aktuella värdet på utspänningen. Detta input register
åsidosätts av holding register 31 om styrning av utgångsåsidosättning (holding
register 8) är aktiverad. När kontrollen av utgångsöverstyrning är inaktiverad
visar detta input register värdet på utgångsspänningen beroende på valt driftläge.
Utspänningsvärdena varierar mellan 30—100 % Us (69—230 VAC). "0" (0 VAC)
indikerar att styrenheten är avstängd.
Input register 3 visar typen av analog insignal. Detta input register denieras av
holding register 11 eller hårdvaruinställningen av position 4 på DIP-omkopplaren.
Värdena är '0' (för 0—20 mA) eller '1' (för 010 VDC).
Input register 4 visar det valda läget för den analoga ingången. Detta input register
definieras av holding register 12 eller hårdvaruinställningen av position 1 på DIP-
omkopplaren (Fig. 4), beroende på valt driftläge. Värdena är '0' (för fallande läge)
eller '1' (för stigande läge).
Input register 5 visar värdet på den maximala utspänningen. Detta input register
definieras av holding register 13 eller hårdvaruinställningen för max.-trimmern (Fig.
6), beroende på valt driftläge. Registervärdena ligger i intervallet 75—100 (75—100
% Us VAC).
Input register 6 visar värdet på den minsta utspänningen. Detta input register
definieras av holding register 14 eller hårdvaruinställningen för min. trimmern (Fig.
7), beroende på valt driftläge. Registervärdena ligger i intervallet 30—70 % Us.
Input register 7 ger information om tillståndet för off-nivån. I Fristående läge
innehåller det värdet inställt av position 2 på DIP-omkopplaren (Fig. 4). I Modbus-
läge innehåller det värdet av holding register 15. Det kan vara '0' (inaktiverat) eller
'1' (aktiverat).
Input register 8 ger information om värdet på off-nivån. I Fristående läge innehåller
det det värde som ställts in av trimmern för OFF-nivå (Fig. 4). I Modbus-läge
innehåller det det värde som ställts in av holding register 16. Detta värde beror på
den valda analoga ingångstypen och läget. Registervärdena kan variera från 0 till
40 (04,0 VDC / 08,0 mA) och från 60 till 100 (6,010,0 VDC /12,0—20,0 mA).
Värdena beror på den valda analoga ingångstypen och läget.
Input register 9 ger information om direktstart eller mjukstart. I fristående läge
motsvarar värdet starttypen som sllts in av position 3 på DIP-omkopplaren.
I Modbus-läge innehåller det det värde som ställts in av holding register 17.
Registervärdena är '0' (för mjukstart) eller '1' (för direktstart).
Input register 10 visar tillståndet för ärrkontrollingången. När den är inaktiverad
fungerar enheten i normalt driftläge. När ärrkontrollingången är aktiverad är
styrenheten i standby-läge. Registervärdena är '0' (för inaktiverat) eller '1' (för
aktiverat).
Input register 12 visar statusen för den oreglerade utgången L1. När den
analoga insignalen är under värdet för avstängningsnivån (om aktiverad) eller när
ärrkontrollens ingång är inaktiverad, är utspänningen för den oreglerade utgången
L1 '0' = OFF (0 VAC). Annars är den 1 = On (230 VAC).
Input register 13 visar larm-LED:ns driftstatus. När den röda LED:n lyser är
registervärdet '1'. När lysdioden är släckt är registervärdet ’0’.
Input register 14 visar enhetens driftsstatus. När registervärdet är 0 (Av) är
styrenheten avstängd. ON / Stand-by-lysdioden på frontpanelen är släckt. Se Fig.
10 Driftsindikering.
När värdet är '1' (On) arbetar styrenheten enligt styralgoritmen och den analoga
insignalen ligger över det valda off-nivåvärdet (om det är aktiverat). ON/Standby-
lysdioden (Fig. 10) lyser konstant.
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 15 - 16
tillbaka till innehållsförteckningen
ON/Stand-by-lysdioden blinkar och registervärdet är "2" (stand-by) när off-nivån är
aktiverad och den analoga insignalen ligger under värdet för off-level.
Holding register (se tabell 1 Modbus registerlista)
Dessa register är läs- / skrivregister och de kan hanteras via kommandona "Läsa
holding register", "Skriva enstaka register" och "Skriva flera register". De är
organiserade i delar som innehåller olika typer av information. De register som inte
används är skrivskyddade. Skrivning i dessa register returnerar inte Modbus-fel,
men det ändrar inte heller något.
Del 1:
Denna del innehåller informa tion om enheten och Modbus kommunikationsins tällningar.
Holding register 1 innehåller adressen där styrenheten svarar på Modbus-
huvudenheten. Standardadressen är "1". Du kan ändra det på två sätt:
Skicka kommandot "Skriva enstaka register" med adress '1' och skriv det nya
adressvärdet.
Anslut endast din enhet till en huvudstyrenhet eller PC-applikation och skicka
kommandot "Skriva enstaka register" till adress '0' (Modbus-sändningsadress) och
skriv ett nytt adressvärde.
De två följande registren (2 och 3) innehåller Modbus-inställningar. Genom att ändra
dessa register ändrar du kommunikationsinställningarna. Standardinställningarna
för Modbus är 19200-E-1 enligt vad som anges i Modbus Protocol Specification.
De följande tre registren (4, 5 och 6) är skrivskyddade. De innehåller information
om hårdvaru- och firmwareversionerna.
Holding register 7 ställer in styrenhetens driftläge. Det finns två alternativ:
Fristående-läge och Modbus-läge. I fristående läge styrs styrenheten helt av
den analoga insignalen och de valda hårdvaruinställningarna. I Modbus-läge kan
inställningarna styras av Modbus huvudstyrenheten.
Holding register 8 används för överstyrning av utgång. Inställningen används för
att åsidosätta utspänningen med ett förvalt värde. Detta värde har högre prioritet
än den beräknade utspänningen för den integrerade regleralgoritmen. Endast
direktstart / mjukstart kan ändra utspänningsvärdet.
Holding register 9 och 10 används inte. De är skrivskyddade.
Del 2:
Holding register 11 ställer in typen av analog insignal. Standardvärdet är '1'
(0–10 VDC); '0' är för 0—20 mA.
Holding register 12 definierar det stigande / fallande analoga ingångsläget.
Standardvärdet '1' är för 0—10 VDC (stigande spänningssignal). Registervärdena är
'0' för 100 VDC och '1' för 010 VDC när snningssignal väljs, och '0' för 20—0 mA
och '1' för 0—20 mA när strömsignal väljs.
Holding register 13 innehåller maximal utspänning. Standardvärdet är '100' (100 %
Us eller 230 VAC). Registervärdena varierar mellan 75—100 (75—100 % Us).
Holding register 14 innehåller den lägste utspänningen. Standardvärdet är "30"
(30 % Us). Registervärdena varierar mellan 3070 (3070 % Us).
Holding register 15 anger status för avstängd nivå. Standardvärdet är '0'
(inaktiverat). "1" är för aktiverat.
Holding register 16 definierar avstängningsnivån. Standardvärdet är '0'
(0 VDC). Detta värde beror på vilken typ av analog ingång och vilket läge som valts.
Registervärdena varierar mellan 0—40 (0— 4,0 VDC) för stigande spänningssignal
och 60100 (6,0— 10,0 VDC) för fallande spänningssignal. När strömsignal väljs
ligger registervärdena mellan 0—40 (0—8,0 mA) för stigande signal och 60100
(12,0—20,0 mA) för fallande signal.
Holding register 17 ställer in direktstart eller mjukstart. Standardvärdet är '1'
(direktstart); "0" är för mjukstart.
Holding register 18 innehåller varaktighetstiden för direktstart eller mjukstart.
Standardvärdet är '10' (10 sekunder). Registervärdena varierar från '0' till '60' (0—60
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING
www.sentera.eu
MIW-MVSS-SV-000 - 06 / 06 / 2023 16 - 16
tillbaka till innehållsförteckningen
sekunder). Den här inställningen är endast tillgänglig i Modbus-läge.
Holding register 19 väljer funktion av ärrstyrd ingångskontroll. Standardvärdet
är '0' för normalt läge. Värdet '1' är för timerläge. Den här inställningen är endast
tillgänglig i Modbus-läge. Off level-läget används inte i timerläget.
Holding register 20 väljer funktion för analog ingång. Standardvärdet är '0' för
normalt läge; '1' är för logikläge. Den här inställningen är endast tillgänglig i Modbus-
läge.
Holding register 21 ställer in värdet för drifttimern. Detta holding register är endast
tillgängligt i timerläge och / eller logikläge. Standardvärdet är '60' (60 sekunder).
Registervärdena kan variera från 0 till 200 (0—200 sekunder). Den här inställningen
är endast tillgänglig i Modbus-läge. Arbetstiden är lika med summan av varaktigheten
för direktstart/mjukstart och tidsvärdet för drifttimern. När en arbetstid har löpt ut
kan enheten endast startas om med hjälp av ärrkontrollen eller en analog ingång.
Nästa holding register 22—30 används inte. De är skrivskyddade.
Holding register 31 åsidosätter utspänningsvärdet i Modbus-läge när
utgångsöverstyrning är aktiverad. Inställningen av överstyrningsvärdet är inte
beroende av de andra inställningarna, förutom valet av direktstart eller mjukstart.
Standardvärdet är '0' (VAC). Registervärdet kan variera mellan 30—100 (30100 %
Us). Det kan också vara ’0’ (0 % Us).
De sista holding registren 32—40 används inte. De är skrivskyddade.
TRANSPORT OCH LAGRING
Undvik vibrationer och extrema förhållanden. Förvara i originalförpackning.
GARANTI OCH BEGRÄNSNINGAR
Två år från leveransdatum mot tillverkningsfel. Ändringar eller omvandlingar av
produkten efter publiceringsdatumet fritar tillverkaren från allt ansvar. Tillverkaren
ansvarar inte för tryckfel eller fel i ovanstående data.
UNDERHÅLL
Under normala förhållanden är denna produkt underhållsfri. Rengör med en torr
eller fuktig trasa om den är smutsig. Vid kraftig förorening, renr med en icke
aggressiv produkt. Under dessa omständigheter bör enheten kopplas bort från
strömförsörjningen. Var uppmärksam på att inga vätskor kommer in i enheten.
Anslut den bara till elnätet igen när den är helt torr.
MVSS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
MED TK FÖR DIN-SKENMONTERING