DPD DUBBEL DIFFERENSTRYCKSGIVARE
HOLDING REGISTER
Data type Description Data Default Values
1Modbus Slave Address unsigned int. Modbus device address 1—247 1
2Modbus Baud Rate unsigned int. Modbus communication
baud rate 1—3 21 =
2 =
3 =
9.600
19.200
38.400
3Modbus Parity Mode unsigned int. Parity check mode 0 = 8N1
1 = 8E1
2 = 8O1 10 =
1 =
2 =
8N1
8E1
8O1
4Device type unsigned int. Device type (Read only)
DPD-X-1K0 = 1071
DPD-X-2K0 = 1072
DPD-X-4K0 = 1073
DPD-X-10K = 1074
5HW version unsigned int. Hardware version of the
device (Read only) XXXX 0100 = 0 x HW version 1.00
6FW version unsigned int. Firmware version of the
device (Read only) XXXX 0100 = 0 x FW version 1.00
7-10 Reserved, returns 0
11 Output Type
(Channel 1) unsigned int. Valbar utgångstyp: 1—3 11 =
2 =
3 =
0—10 VDC
0—20 mA
PWM
12 Pressure Range Minimum
(Channel 1) unsigned int. Minimum pressure for
analog output 1 0—10.000 0 1.000 = 100.0 Pa
1.000 Pa
(DPD-X-10K )
13 Pressure Range Maximum
(Channel 1) unsigned int. Maximum pressure for
analog output 1
DPD-X-1K0
DPD-X-2K0
DPD-X-4K0
50—10.000 Pa
50—20.000 Pa
50—40.000 Pa 10.000 1.000 = 100.0 Pa
DPD-X-10K 50—10.000 Pa 1.000 = 100.0 Pa
14 Response Time (Channel 1) unsigned int. Channel 1 response time 1—100 10 10 = 1 s
15 Min. Pressure Limit (Channel
1) unsigned int. Channel 1 minimum
pressure limit
DPD-X-1K0
DPD-X-2K0
DPD-X-4K0
0—10.000
0—20.000
0— 40.000 01.000 = 100.0 Pa
DPD-X-10K 0—10.000 01.000 = 100.0 Pa
16 Max. Pressure Limit
(Channel 1) unsigned int. Channel 1 maximum
pressure limit
DPD-X-1K0
DPD-X-2K0
DPD-X-4K0
0—10.000
0—20.000
0— 40.000
10.000
20.000
40.000 1.000 = 100.0 Pa
DPD-X-10K 0—10.000 10.000 1.000 = 100.0 Pa
17 Power-up Timer
(Channel 1) unsigned int. Channel 1 power-up timer.
It counts the time before
the first detection 0—1.000 s 60 s 100 = 100 s
18 K-factor Selection (Channel
1) unsigned int. Channel 1 K-factor
selection according to the
motor type 0—1.000 0
19 Internal Voltage Source
PWM (Channel 1) unsigned int. Channel 1 internal voltage
source selection for the
PWM 1 output 0—1 00 =
1 = 0 = 3,3 VDC
1 = 12 VDC
20 Network Bus Termination
(NBT) unsigned int. Network bus termination
resistor state 0—1 00 =
1 = Disconnected
Anslutningar
21 Output Type (Channel 2) unsigned int. Select channel 2 output
type 1—3 11 =
2 =
3 =
0—10 VDC
0—20 mA
PWM
22 Pressure Range Minimum
(Channel 2) unsigned int. Minimum pressure for
analog output 2 0—10.000 01.000 = 100.0 Pa
1.000 = 1.000 Pa
(DPD-X-10K )
23 Pressure Range Maximum
(Channel 2) unsigned int. Maximum pressure for
analog output 2
DPD-X-1K0
DPD-X-2K0
DPD-X-4K0
50—10.000 Pa
50—20.000 Pa
50—40.000 Pa 10.000 1.000 = 100.0 Pa
DPD-X-10K 50—10.000 Pa 100.0 Pa
24 Response Time (Channel 2) unsigned int. Channel 2 response time 1—100 10 10 = 1 s
25 Min. Pressure Limit
(Channel 2) unsigned int. Channel 2 minimum
pressure limit
DPD-X-1K0
DPD-X-2K0
DPD-X-4K0
0—10.000
0—20.000
0— 40.000 0 1.000 = 100.0 Pa
DPD-X-10K 0—10.000 01.000 = 100.0 Pa
26 Max. Pressure Limit
(Channel 2) unsigned int. Channel 2 power-up timer.
It counts the time before
the first detection
DPD-X-1K0
DPD-X-2K0
DPD-X-4K0
0—10.000
0—20.000
0— 40.000
10.000
20.000
40.000 1.000 = 100.0 Pa
DPD-X-10K 0—10.000 10.000 100.0 Pa
27 Power-up Timer (Channel 2) unsigned int. Channel 2 power-up timer.
It counts the time before
the first detection 0—1.000 s 60 s 100 = 100 s
28 Valbar utgångstyp: unsigned int. Channel 2 K-factor
selection according to the
motor type 0—1.000 0
29 Internal Voltage Source
PWM (Channel 2) unsigned int. Channel 2 internal voltage
source selection for the
PWM 1 output 0—1 00 =
1 = 0 = 3,3 VDC
1 = 12 VDC
30 Display Mode Selection unsigned int. Display Mode Selection 0-2 00 =
1 = Disconnected
Anslutningar
Om du vill veta mer om Modbus över seriell linje, besök: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
TRANSPORT OCH LAGRING
Undvik vibrationer och extrema förhållanden. Förvara i originalförpackning.