Sentera Controls MVS-1-60CDM Mounting Instruction

Typ
Mounting Instruction
MVS ELEKTRONISK
FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
Installations- och bruksanvisning
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 2 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
Innehållsförteckning
KERHET OCH FÖRSIKTIGHETSÅTGÄRDER 3
PRODUKTBESKRIVNING 4
ARTIKELKODER 4
AVSETT ANVÄNDNINGSOMRÅDE 4
TEKNISKA DATA 4
STANDARDER 5
LEDNINGAR OCH FÖRBINDELSER 5
DRIFTSDIAGRAM 5
INSTALLATIONSANVISNINGAR I STEG 7
VERIFIERING AV INSTALLATION 10
BRUKSANVISNING 11
MODBUS REGISTERLISTA 12
TRANSPORT OCH LAGRING 16
GARANTI OCH BEGRÄNSNINGAR 16
UNDERLL 16
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 3 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
SÄKERHET OCH FÖRSIKTIGHETSÅTGÄRDER
Läs igenom all information, databladet, Modbus registerlista, installations- och
bruksanvisningen och betrakta kopplingsdiagrammet innan du börjar arbeta
med produkten. För personlig och utrustningens säkerhet och för optimal
produktprestanda, se till att du förstår innehållet innan du installerar, använder
eller underhåller produkten.
Av säkerhets- och godkännandeskäl (CE) är inga obehöriga omvandlingar och/eller
modifikationer av produkten tillåtna.
Produkten får inte utsättas för onormala förhållanden såsom extrema
temperaturer, direkt solljus eller vibrationer. Långvårig exponering för kemiska
ångor i hög koncentration kan påverka produktens prestanda. Håll arbetsplatsen
så torr som möjligt, se upp för kondens.
Alla installationer ska följa lokala hälso- och säkerhetsföreskrifter, lokala
elektriska standarder och godkända koder. Produkten får bara installeras av en
ingenjör eller tekniker som har expertkunskaper om produkten och de nödvändiga
försiktighetsåtgärderna.
Undvik kontakt med påslagna elektriska komponenter. Koppla alltid bort
strömförsörjningen innan du ansluter, underhåller eller reparerar produkten.
Kontrollera att du väljer rätt strömförsörjning till produkten och att du använder
kablar med rätt storlek och egenskaper. Se till att alla skruvar och muttrar är väl
åtdragna och att eventuella säkringar sitter på plats.
Utrustningen och förpackningen kan återvinnas och ska bortskaffas i enlighet med
lokala och nationella lagar och bestämmelser.
Om du har ytterligare frågor, kontakta din tekniska support eller rådfråga en
expert.
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 4 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
PRODUKTBESKRIVNING
MVS-serien styr hastigheten hos enfas spänningsstyrbara elmotorer (230 VAC /
5060 Hz) baserat på en standard insignal. De är utrustade med Modbus RTU-
kommunikation och förser många funktioner: alternativ för ärrkontroll, justerbar
off-nivå, min. och max. inställningar för utspänning och tidsbegränsad motordrift
som initieras av en logik eller en omkopplingssignal.
ARTIKELKODER
Kod Nominell stm, [A] Säkringsvärde [A]
kring 1 kring 2
MVS-1-15CDM 1,5
F 0,315 A H 250
V (5*20 mm)
F 3,15 A H 250 V
(5*20 mm)
MVS-1-30CDM 3,0 F 5,0 A H 250 V
(5*20 mm)
MVS-1-60CDM 6,0 F 10,0 A H 250 V
(5*20 mm)
MVS-1100CDM 10,0 F 16,0 A H 250 V
(6,3*32 mm)
AVSETT ANVÄNDNINGSOMRÅDE
Fläkthastighetsreglering i ventilationssystem
Applikationer där Modbus -kommunikation eller en timerfunktion behövs
Endast för inomhusbruk
TEKNISKA DATA
Strömrsörjning: 230 VAC ±10 %/50—60 Hz
Analog ingång:
spänning: 0—10 VDC
ström: 0—20 mA
Analoga ingångslägen: stigande eller fallande
Funktionalitet för analog ingång: Normalt läge / Logik-läge
Ingång för ärrkontroll: normal eller timerfunktion
Reglerad utgång: 30100 % Us
Max. utgångsbelastning: beror på versionen (se tabellen ovan).
Oreglerad utgång, L1: 230 VAC / 5060 Hz/max. 2 A
Inställning av min. utspänning, Umin: 3070 % Us, kan väljas med trimmer eller via
Modbus
Inställning av max. utspänning, Umax: 75—100 % Us, valbar med trimmer eller via
Modbus
O-nivå, justerbar med trimmer eller via Modbus:
0—4 VDC/08 mA för stigande läge
106 VDC/2012 mA för fallande läge
Direktstart eller mjukstart
Lågspänningsutgång: + 12 VDC / 1 mA för extern potentiometer
Modbus kommunikation
Driftsindikering:
kontinuerligt grön: normal drift
blinkande grön: vänteläge
Överspännings- och överströmsskydd
Kapsling:
Gränssnittsmodul för DIN-skenmontering: polyamid - PA UL94V0; grön (RAL 6017)
Omslag: plexiglas, transparent
Kapslingsklass: IP20 (enligt EN60529)
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 5 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
Omgivningsförhållanden vid drift:
temperatur: -20—40 °C
relativ luftfuktighet: < 80 % rH (icke-kondenserande)
Förvaringstemperatur: -40—50 °C
STANDARDER
Lågspänningsdirektiv 2014/35/EU
EMC-direktiv 2014/30/EU
RoHs-direktiv 2011/65/EU
LEDNINGAR OCH FÖRBINDELSER
Ltaggregat 230 VAC ±10% / 5060 Hz
NNeutralledare
PE Jordterminal
L1 Oreglerad utgång (230 VAC / max. 2 A)
U1, U2 Reglerad utgång till motor
SW Omkopplare för ärrstyrning / timer
+V Uteffekt + 12 VDC / 1 mA
Ai
Analog ingång:
(010 VDC/0—20 mA) eller (100 VDC/20—0 mA)
Indata logik (timerfunktionalitet):
(minst 2,5VDC och > 30 ms)
GND Jord
AModbus RTU (RS485), signal A
/B Modbus RTU (RS485), signal /B
Anslutningar Kabeltvärsnitt: max 2,5mm2
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 6 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
DRIFTSDIAGRAM
Normalt / Fjärrstyrt driftläge
Stigande ingångsläge Fallande ingångsläge
Avstängd nivå inaktiverad
U
out
,
[%]
10 VDC
20 mA
Umax
Umin
0
Ai,
[VDC]/[mA]
100
75
70
30
Umax
område
Umin
område
U
out
,
[%]
10 VDC
20 mA
Umax
Umin
0
Ai,
[VDC]/[mA]
100
75
70
30
Umax
område
Umin
område
Beräkningsformel
för stigande läge
Uout=Umin+ Aimax
Ai
(Umax-Umin)
Beräkningsformel
för fallande läge
Uout=Umax- Aimax
Ai
(Umax-Umin)
Umax
Umin
0
,Ai
[VDC]
/
[mA]
4 VDC
8 mA
U,
[%]out
100
75
70
30
10 VDC
20 mA
Umax
Område
Umin
område
område
Off-nivå
Umax
Umin
0
,Ai
[VDC] /
[mA]
10 VDC
20 mA
6 VDC
12 mA
U, [%]out
100
75
70
30
Umax
Område
Umin
område
Off-nivå
Avstängd nivå aktiverad
Beräkningsformel
för stigande läge
Uout=Umax+ Aimax-Off level
Ai-Off level (Umax-Umin)
Beräkningsformel
för fallande läge
Uout=Umax- Aimax-Off level
Ai-Off level (Umax-Umin)
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 mA
Uout, [%]
100
75
70
30
0 VDC / 0 m
Umax
område
Umin
område
Direktstart varaktighet
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 m
Uout, [%]
100
75
70
30
0 VDC / 0 mA
Umax
område
Umin
område
Direktstart varaktighet
Direktstart aktiverad
t [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
10 VDC /
20 mA
Ai,
[VDC]/
[mA]
Umax
område
Umin
område
Mjukstart varaktighet
Off-nivå
t [s]
Umax
Umin
Uout, [%]
100
75
70
30
10 VDC /
20 mA
0 VDC /
0 mA
Ai,
[VDC]/
[mA]
Umax
område
Umin
område
Mjukstart varaktighet
Off-nivå
Mjukstart aktiverad
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 7 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
Stigande ingångsläge Fallande ingångsläge
Mjukstart och avstängt läge
t [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
10 VDC /
20 mA
Ai,
[VDC]/
[mA]
Umax
område
Umin
område
Mjukstart varaktighet
Off-nivå
t [s]
Umax
Umin
Uout, [%]
100
75
70
30
10 VDC /
20 mA
0 VDC /
0 mA
Ai,
[VDC]/
[mA]
Umax
område
Umin
område
Mjukstart varaktighet
Off-nivå
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 mA
Uout, [%]
100
75
70
30
0 VDC / 0 m
Umax
område
Umin
område
Direktstart varaktighet
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 m
Uout, [%]
100
75
70
30
0 VDC / 0 mA
Umax
område
Umin
område
Direktstart varaktighet
Direktstart & avstängt läge
Timer modus Logik modus
0
t, [s]
5 VDC
2,5 VDC
Fjärrstyrning
Strömbrytare
[VDC]
Standby I drift
Spänning
amplitud
område
Kontrollsignal brytare
t [s]
0
U
out, [%]
100
75
Umax
område
Direktstart varaktighet Drift timer Regulatorn är
avstängd
Direktstart aktiverad
Mjukstart aktiverad
t
t
t
t
SW
Holding
register
18
Holding
register
21
Mjukstart
varaktighet
Mjukstart
varaktighet
Start
Utgång
Umax
Timer
Mjukstart
StoppStartStopp
Drift
timer
Driftstid
Holding
register
18
AV AV
Brytare kontrollsignal
t
t
t
t
Ai >2,4 VDC
Holding
register
18
Holding
register
21
Holding
register
21
Mjukstart
varaktighet Mjukstart
varaktighet
Start
Utgång
Umax
Timer
Mjukstart
Start Stopp
Drift
timer Drift
timer
Holding
register
18
AV AV
Ai-kontrollsignal
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 8 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
INSTALLATIONSANVISNINGAR I STEG
Innan du börjar montera MVS-styrenheten, läs noggrant "Säkerhet och
försiktighetsåtgärder". Forttt sedan med följande steg:
1. Stäng av strömförsörjningen.
2. Ta bort det genomskinliga locket på kapslingen.
3. Ta bort skruvarna på sidorna av modulen. Skjut modulen längs styrskenorna på en
standard DIN-skena. Fäst på önskad position på skenan genom att montera höljets
sidor. Tänk pått monteringsmått (Fig. 1) och monteringsposition (Fig. 2).
Fig. 1 Monteringsmått
MVS-1-60CDM
MVS-1100CDM
MVS-1-15CDM
MVS-1-30CDM
H
L
W
Artiklar Höjd [mm] Längd [mm] Bredd [mm]
MVS-1-15CDM,
MVS-1-30CDM 96 127
112
MVS-1-60CDM,
MVS-1100CDM 128
Fig. 2 Monteringsposition
DIN-skena
4. Anslut motorn / fläkten.
5. Anslut L1-utgången för en 3-trådsanslutning, styrd ventil osv. (om nödvändigt).
Se Fig. 3b 3-tråds motoranslutning.
Fig. 3 Ledningar och förbindelser
Brytare för
ärrkontroll
Modbus RTU A
/B
Analog ingång
010 VDC / 0—20 mA
Utgång
strömförsörjning
+12 VDC / 1 mA
L
N
PE
Oreglerad
utdata
230 VAC / max. 2 A.
M
1
Matning
230 VAC ,
5060 Hz
3a 2-tråds motoranslutning
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 9 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
Matning
230 VAC,
5060 Hz
Brytare för
ärrkontroll
Modbus RTU A
/B
Analog ingång
010 VDC / 0—20 mA
Utgång
strömförsörjning
+12 VDC / 1 mA
L
N
PE M
1
3b 3-tråds motoranslutning
6. Välj önskad analog ingångstyp och läge, startläge och OFF-nivåläge med DIP-
omkopplaren på kortet. (Se Fig. 4 Inställningar DIP-omkopplare).
Fig. 4 Inställningar DIP-omkopplare
Välj stigande/fallande läge
(DIP-switch, position 1)
1 2 3 4
På – Fallande modus:
10—0 VDC/20—0 mA
Av – Stigande modus:
0—10 VDC/0—20 mA
Välj Off-ni
(DIP-switch, position 2)
1 2 3 4
På – aktiverad
Av – inaktiverad
Välj direktstart / mjukstart
(DIP-switch, position 3)
1 2 3 4
På – Direktstart
Av – Mjukstart
Välj ingångsmodus
(DIP-switch, position 4)
1 2 3 4
PÅ - Stmläge
(0–20 mA)
AV - Spänningsläge
(0–10 VDC )
7. Kontrollera om enheten startar eller avslutar nätverket (se Exempel 1 och
Exempel 2). Om den gör det, sätt NBT-bygeln på stiften. Om den inte gör det,
anslut inte bygeln (se Fig. 5).
Exempel 1 Exempel 2 Fig. 5 Bygel för Network
Bus Terminator
RX
ТX
NBT
NBT
Slave 2
Master Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
Om en AC-nätaggregat används med någon av enheterna i ett Modbus-
nätverk bör GND-terminalen INTE anslutas till andra enheter i nätverket eller
via CNVT-USB-RS485-omvandlaren. Detta kan orsaka permanenta skador på
kommunikationshalvledare och / eller datorn.
VARNING
8. Anslut strömförsörjningskabeln.
9. Justera maximal hastighet med trimmer (vid behov). Standardinställningen är Us
(230 VAC) - se Fig. 6.
10. Justera minimi hastighet med trimmer (vid behov). Standardinställningen är 30 %
Us (69 VAC) - se Fig. 7.
11. Justera avstängd nivå med trimmer (vid behov). Standardinställningen är 0 VAC)
- se Fig. 8.
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 10 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
Fig. 6 Max. hastighetstrimmer Fig. 7 Min. hastighetstrimmer Fig. 8 Trimmer avstängd nivå
12. Stäng höljet och fixa det genomskinliga locket.
13. Slå på strömförsörjningen.
14. Anpassa fabriksinställningarna till de önskade via programvaran 3SModbus eller
Sensistant (vid behov). För fabriksinställningar, se Tabell Modbus registerlista.
VERIFIERING AV INSTALLATION
Följ instruktionerna nedan:
1. Slå på strömförsörjningen.
2. Ställ in NBT-bygeln, DIP-omkopplaren, max. trimmer, min. trimmer och trimmer för
avstängd nivå på önskade positioner / värden. Fabriksinställningarna är följande:
NBT-bygeln är öppen (NBT-motståndet är frånkopplat)
Stigande läge: 010 VDC / 0—20 mA
Avstängt läge = AV
Mjukstart aktiverad
Inspänningsläge (010 VDC)
Min. inställning av min. hastighetstrimmer = 30% av Us
Max. inställning av max. hastighetstrimmer = Us
Min. inställning av trimmer för avsngd nivå = 0 VDC
3. Ställ in den analoga ingångssignalen till maxvärdet 10 VDC eller 20 mA.
4. Den anslutna motorn körs med högsta eller minsta hastighet beroende på det analoga
ingångsläget (stigande / fallande).
5. Om OFF-nivå är aktiverad och fallande analogt ingångsläge väljs slutar motorn att gå.
6. Ställ in den analoga ingångssignalen till maxvärdet 0 VDC eller 0 mA.
7. Den anslutna fläkten körs med lägsta eller högsta hastighet beroende på analogt
ingångsläge (stigande / fallande).
8. Om OFF-nivån är aktiverad och stigande analogt ingångsläge väljs slutar motorn att
gå.
9. Om OFF-nivån är aktiverad och ingångssignalen är lika med värdet för OFF-nivån
kommer motorns hastighet att vara den lägsta hastigheten i stigande läge eller den
högsta hastigheten i fallande läge.
10. Om styrenheten inte fungerar enligt anvisningarna ovan måste kabelanslutningarna
och inställningarna kontrolleras.
11. Kontrollera om båda lysdioderna (Fig. 9) blinkar när du har slagit på enheten. Om
de gör det har din enhet upptäckt Modbus -tverk. Om de inte gör det kontrollera
anslutningarna igen.
Fig. 9 Detektering av kommunikation
Lysdiodernas status kan endast kontrolleras när enheten är strömsatt. Vidta
relevanta säkerhetsåtgärder.
VARNING
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 11 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
BRUKSANVISNINGAR
DRIFTLÄGEN
I Modbus-läge styr du parametrarna: Umax, Umin, Direktstart / Mjukstart, avstängd
nivå aktiverad/inaktiverad och värde avstängd nivå via Modbus register.
I fristående läge styr du parametrarna: Umax, Umin, Direktstart / Mjukstart,
avstängd nivå aktiverad/inaktiverad och värde avstängd nivå med hjälp av
hårdvaruinställningarna (DIP-switch, trimmers, byglar).
I normalt läge, om O-nivån är inaktiverad utförs mjukstart / kickstart endast en
gång - efter att styrenheten har försetts med stm; i annat fall utförs mjukstart /
kickstart varje gång styrenheten slås på.
När Timerläget är valt, tar styrenheten emot en pulsstyrsignal från omkopplaren
för ärrkontroll. När logikläget är valt, tar styrenheten emot en pulsstyrsignal från
Ai-ingången.
I båda lägena (Timerläge och Logikläge) ska pulsbredden vara mer än 30 ms annars
filtreras signalen.
LED-DRIFTSINDIKERING
När den gröna lysdioden - Fig. 10 - lyser fungerar styrenheten i normalt läge. När
den blinkar:
fungerar styrenheten i ärrstyrningsläge eller
är Off-nivån aktiverad och ligger den analoga insignalen under OFF-nivåvärdet.
Fig. 10 Driftsindikation
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 12 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
MODBUS REGISTERLISTA
INPUT REGISTERS
Data type Description Data Values
1Analog input level unsigned int. Analog input value depending on the selected analog
input type. 0—100
0 =
100 =
0 =
100 =
0 VDC
10,0 VDC
or
0 mA
20,0 mA
2Current output voltage unsigned int. Actual output voltage 0,
30—100
0 =
30 =
100 =
0 % Us
30 % Us
100 % Us
3Analog input type unsigned int. Type of the selected analog input 0—1 0 =
1 =
0—20 mA
0—10 VDC
4Ascending/descending
input mode unsigned int. Ascending or descending analog input mode depending
on the selected analog input type. 0—1
0 =
1 =
0 =
1 =
100 VDC
0—10 VDC
or
200 mA
0—20 mA
5Maximum output
voltage unsigned int. Maximum output voltage 75—100 75 =
100 =
75 % Us
100 % Us
6Minimum output
voltage unsigned int. Minimum output voltage 30—70 30 =
70 =
30 % Us
70 % Us
7 Enable off level unsigned int. Enables off level 0—1 0 =
1 =
Disabled
Enabled
8Off level value unsigned int.
Off level value depending on the selected analog
input type and ascending / descending analog input
mode.
0 — 40
60—100
Ascending mode:
0 =
400 =
0 =
200 =
Voltage
0 VDC
4,0 VDC
Current
0 mA
8,0 mA
Descending mode:
100 =
60 =
100 =
60 =
Voltage
10,0 VDC
6,0 VDC
Current
20,0 mA
12,0 mA
9 Kick start/soft start unsigned int. Selects kick start or soft start 0—1 0 =
1 =
Soft start
Kick start
10 Remote control input unsigned int. Remote control input 0—1 0 =
1 =
Disabled
Enabled
12 L1 control unsigned int. L1 control 0—1 0 =
1 =
Off
On
14 ON/Stand-by LED unsigned int. ON/Stand-by LED 0—2
0 =
1 =
2 =
Off
On
Stand-by
15-20 Reserved, returns 0
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 13 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
HOLDING REGISTERS
Data type Description Data Default Values
1Device slave
address unsigned int. Modbus device address 1—247 1
2Modbus baud
rate unsigned int. Modbus communication baud rate 1—4 2
1 =
2 =
3 =
4 =
9.600
19.200
38.400
57.600
3Modbus parity unsigned int. Parity check mode 0—2 1
0 =
1 =
2 =
8N1
8E1
8O1
4Device type unsigned int. Device type (Read only)
MVS-CDM = 3009
5HW version unsigned int. Hardware version of the device (Read only) XXXX 0 x 0300 = HW version 3.00
6FW version unsigned int. Firmware version of the device (Read only) XXXX 0 x 0140 = FW version 1.40
7Operating mode unsigned int. Enables Modbus control and disables the DIP switch and
trimmers 0—1 00 =
1 =
Standalone
mode
Modbus
mode
8Output override unsigned int. Enables the direct control over the output. Always
settable. Active only if holding register 7 is set to 1. 0—1 00 =
1 =
Disabled
Enabled
9-10 Reserved, returns 0
11 Analog input
type unsigned int. Selects the analog input type of the device. Always
settable. Active only if holding register 7 is set to 1. 0—1 10 =
1 =
0—20 mA
0—10 VDC
12
Ascending/
descending
analog input
mode
unsigned int.
Ascending/descending analog input mode. Depends on
the selected analog input type. Always settable. Active
only if holding register 7 is set to 1.
0—1 1
0 =
1 =
0 =
1 =
100 VDC
010 VDC
or
200 mA
0—20 mA
13 Maximum
output voltage unsigned int. Maximum settable output voltage. Always settable.
Active only if holding register 7 is set to 1. 75—100 100 75 =
100 =
75 % Us
100 % Us
14 Minimum output
voltage unsigned int. Minimum settable output voltage. Always settable.
Active only if holding register 7 is set to 1. 30—70 30 30 =
70 =
30 % Us
70 % Us
15 Enable off level unsigned int. Enables off level. Always settable. Active only if holding
register 7 is set to 1. 0—1 00 =
1 =
Disabled
Enabled
16 Off level value unsigned int.
Off level value. Depends on the selected analog input type
and ascending/descending analog input mode. Always
settable. Active only if holding register 7 is set to 1.
0—40
60—100 0
Ascending mode:
0 =
40 =
0 =
40 =
Voltage
0 VDC
4,0 VDC
Current
0 mA
8,0 mA
Descending mode:
100 =
60 =
100 =
60 =
Voltage
10,0 VDC
6,0 VDC
Current
20,0 mA
12,0 mA
17 Kick start/soft
start unsigned int. Selects kick start or soft start. Always settable. Active
only if holding register 7 is set to 1. 0—1 10 =
1 =
Soft start
Kick start
18 Kick start/soft
start duration unsigned int. Sets the duration time. Always settable. Active only if
holding register 7 is set to 1. 0—60 10 0 =
60 =
0 s
60 s
19 Remote control
functionality unsigned int.
Sets the remote control input mode. Depends on the
selected kick start or soft start mode. Always settable.
Active only if holding register 7 is set to 1.
0—1 00 =
1 =
Normal mode
Timer mode
20 Analog input
functionality unsigned int.
Sets the analog input functionality. Depends on the
selected kick start or soft start. Always settable. Active
only if holding register 7 is set to 1.
0—1 00 =
1 =
Normal mode
Logic mode
21 Operation timer unsigned int.
Sets the operation time of the device when Timer mode
by remote control input or Logic mode by the analog input
is selected. e operation time is additional to the kick
start/soft start duration times. Always settable. Active
only if holding registers 7 and 19 or/and 20 are set to 1.
0—200 60 0 =
200 =
0 s
200 s
22-30 Reserved, returns 0
31 Output override
value unsigned int. Override value for the analog output. Always settable.
Active only if holding register 8 is set to 1.
0,
30—100 0
0 =
30 =
100 =
0 % Us
30 % Us
100 % Us
32-40 Reserved, returns 0
If you want to find out more about Modbus over serial line, please visit: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 14 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
INPUT REGISTER (se tabell 1 Modbus registerlista)
Input register är skrivskyddade. Tabell 1 visar hur uppgifterna är organiserade i Input
registren. De uppmätta uppgifterna börjar fn adress 1 och slutar på adress 14. Övriga
input register används inte. När de adresseras, returnerar de 0.
All data kan läsas med kommandot "Läsa Input Register". Tabell1 visar typen av
returnerade data för varje register och hur den ska tolkas. Till exempel betyder läsning
av "300" i Input register 1 att den uppmätta analoga ingångssignalen är 3,0 VDC (eller
6,0 mA), läsning av "50" i Input register 2 betyder att utspänningen är 50 % Us (115 VAC).
Input register 1 visar det aktuella värdet av den uppmätta analoga ingångssignalen.
Detta värde beror på den valda analoga ingångstypen. När spänningsläge väljs varierar
värdena mellan 0—1.000 (0—10,0 VDC). När strömläge väljs varierar värdena mellan
0—1.000 (0—20,0 mA).
Input register 2 visar det aktuella värdet på utspänningen. Detta input register åsidosätts
av holding register 31 om överstyrning av utdata (holding register 8) är aktiverad. När
denna kontroll är inaktiverad visar detta input register värdet på utspänningen enligt
det valda driftläget. Utspänningsvärdena varierar mellan 30—100 % Us (69—230 VAC).
"0" (0 VAC) indikerar att styrenheten är avstängd.
Input register 3 visar typen av analog insignal. Detta input register definieras av holding
register 11 eller av hårdvaruinställningen för position 4 på DIP-omkopplaren. Värdena är
'0' (r 0—20 mA) eller '1' (för 010 VDC).
Input register 4 visar det valda läget för den analoga ingången. Detta input register
definieras av holding register 12 eller av hårdvaruinställningen för position 1 på DIP-
omkopplaren (Fig. 4), enligt det valda driftläget. Värdena är '0' (för fallande läge) eller
'1' (för stigande läge).
Input register 5 visar värdet på den maximala utspänningen. Detta input register definieras
av holding register 13 eller av hårdvaruinställningen för max.-trimmern (Fig. 6), enligt det
valda driftläget. Registervärdena ligger mellan 75—100 (75—100 % Us VAC).
Input register 6 visar värdet på minsta utspänning. Detta input register definieras av
holding register 14 eller av hårdvaruinställningen för min. trimmer (Fig. 7), enligt det
valda driftläget. Registervärdena ligger mellan 30—70 % us.
Input register 7 ger information om off level-tillståndet. I fristående läge innehåller
den det värde som sllts in i position 2 på DIP-omkopplaren. (Fig. 4). I Modbus-läge
innehåller den värdet av holding register 15. Det kan vara '0' (inaktiverat) eller '1'
(aktiverat).
Input register 8 ger information om off level-värdet. I fristående läge
innehåller den det värde som ställts in av off-nivåtrimmern (Fig. 8). I Modbus-
läge innehåller den det värde som ställts in av holding register 16. Detta
värde beror på den valda analoga ingångstypen och läget. Registervärdena
kan variera från 0 till 40 (04,0 VDC / 0—8,0 mA) och fn 60 till 100
(6,0—10,0 VDC /12,0—20,0 mA). Värdena beror på den valda analoga ingångstypen
och läget.
Input register 9 ger information om direktstart eller mjukstart. I fristående läge
motsvarar värdet starttypen som ställts in av position 3 på DIP-omkopplaren. I Modbus-
läge innehåller den det värde som ställts in av holding register 17. Registervärdena är '0'
(för mjukstart) eller '1' (för direktstart).
Input register 10 visar tillståndet för ärrkontrollens ingång. När den är inaktiverad
fungerar enheten i normalt driftläge. När ärrkontrollens ingång är aktiverad är
styrenheten i standby-läge. Registervärdena är '0' (för inaktiverat) eller '1' (för aktiverat).
Input register 12 visar status för den oreglerade utgången L1. När den analoga
ingångssignalen är under värdet för avstängningsnivån (om den är aktiverad) eller
när ärrstyrningsingången är inaktiverad, är utgångsspänningen för den oreglerade
utgången L1 "0" = OFF (0 VAC). Annars är den ’1’ = På (230 VAC).
Input register 14 visar enhetens driftsstatus. När registervärdet är 0 (Av) är styrenheten
avstängd. Standby-lysdioden är släckt - se Fig. 10. När värdet är '1' (På) arbetar
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 15 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
styrenheten enligt styralgoritmen och den analoga insignalen ligger över det valda
off-nivåvärdet (om det är aktiverat). Stand-by-lysdioden - Fig. 10 - ljsuer kontinuerligt.
Denna lysdiod blinkar och registervärdet är '2' (stand-by) när off-nivån är aktiverad och
den analoga insignalen är under off level-värdet.
HOLDING REGISTER (se tabell 1 Modbus registerlista)
Dessa register är läs- / skrivregister och kan hanteras med kommandot "Läsa Holding
Register", "Skriva enstaka register" och "Skriva flera register". De är organiserade i delar
som innehåller olika typer av information. De register som inte används är skrivskyddade.
Skrivning i dessa register returnerar inte Modbus-fel, men det ändrar inte heller något!
Del 1:
Denna del innehåller information om enheten och Modbus kommunikationsinställningar.
Holding register 1 innehåller den adress där styrenheten svarar på Modbus-
huvudenheten. Standardadressen är "1". Du kan ändra det på två sätt:
1. Skicka kommandot "Skriva enstaka register" med adress '1' och skriv det nya
adressvärdet.
2. Anslut endast din enhet till en huvudstyrenhet eller PC-applikation och skicka
kommandot "Skriva enstaka register" till adress '0' (Modbus-sändningsadress) och
skriv ett nytt adressvärde.
De två följande registren (2 och 3) innehåller Modbus-inställningar. Om du ändrar dessa
register ändrar du kommunikationsinställningarna. Standardinställningarna för Modbus
är 19200-E-1 som anges i Modbus Protocol Specification.
De följande tre registren (4, 5 och 6) är skrivskyddade. De innehåller information om
hårdvaru- och firmwareversionerna.
Holding register 7 ställer in styrenhetens driftläge. Det finns två alternativ: Fristående-
läge och Modbus-läge. I fristående läge styrs styrenheten helt av den analoga insignalen
och de valda maskinvaruinställningarna. I Modbus-läge kan inställningarna styras av
Modbus huvudstyrenheten.
Holding register 8 används för kontroll av åsidosättning av utdata. Inställningen
används för att åsidosätta utspänningen med ett förvalt värde. Detta värde har högre
prioritet på den beräknade utspänningen från den integrerade styralgoritmen. Endast
direktstart / mjukstart kan ändra utspänningsvärdet.
Holding register 9 och 10 används inte. De är skrivskyddade.
Del 2:
Holding register 11 ställer in den analoga insignaltypen. Standardvärdet är '1'
(010 VDC); '0' är för 0—20 mA.
Holding register 12 definierar det stigande / fallande analoga ingångsläget.
Standardvärdet är '1' för 0—10 VDC (stigande spänningssignal). Registervärdena är '0'
för 100 VDC och '1' för 0—10 VDC när spänningssignal väljs, och '0' för 20—0 mA och
'1' för 020 mA när stmsignal väljs.
Holding register 13 innehåller maximal utspänning. Standardvärdet är '100' (100 % Us
eller 230 VAC). Registervärdena varierar mellan 75—100 (75—100 % Us).
Holding register 14 innehåller minsta utspänning. Standardvärdet är "30" (30 % Us).
Registervärdena varierar mellan 30—70 (3070 % Us).
Holding register 15 ställer in off level-tillståndet. Standardvärdet är '0' (inaktiverat). "1"
är för aktiverat.
Holding register 16 definierar off level. Standardvärdet är '0' (0 VDC). Detta värde beror
på den valda analoga ingångstypen och läget. Registervärdena varierar mellan 0—40
(0— 4,0VDC) för stigande spänningssignal och 60—100 (6,0— 10,0 VDC) för fallande
spänningssignal. När strömsignal väljs ligger registervärdena mellan 0—40 (0—8,0 mA)
för stigande signal och 60100 (12,020,0 mA) för fallande signal.
Holding register 17 visar direktstart eller mjukstart. Standardvärdet är '1' direktstart
"0" är för mjukstart.
www.sentera.eu
MIW-MVS-SV-000 - 22 / 03 / 2023 16 - 160
tillbaka till innehållsförteckningen
MVS ELEKTRONISK FLÄKTHASTIGHETSREGULATOR
FÖR DIN-SKENMONTERING
Holding register 18 innehåller start- eller mjukstartstid. Standardvärdet är '10'
(10 sekunder). Registervärdena varierar från '0' till '60' (0—60 sekunder). Den här
inställningen är endast tillgänglig i Modbus-läge.
Holding register 19 väljer ärrkontrollens ingångsfunktionalitet. Standardvärdet är '0'
för normalt läge. Värdet '1' är för timerläge. Den här inställningen är endast tillgänglig i
Modbus-läge. OFF-nivåläge används inte i timerläge.
Holding register 20 väljer den analoga ingångsfunktionen. Standardvärdet är '0' för
normalt läge; '1' är för logikläge. Den här inställningen är endast tillgänglig i Modbus-
läge.
Holding register 21 ställer in värdet på drifttimern. Detta holding register är endast
tillgängligt i timerläge och / eller logikläge. Standardvärdet är '60' (60 sekunder).
Registervärdena kan variera från 0 till 200 (0—200 sekunder). Den här inställningen
är endast tillgänglig i Modbus-läge. Arbetstiden är lika med summan av start- /
mjukstartstiden och tidsvärdet för drifttimern. När en arbetstid löper ut kan endast en
ärrkontrollingång eller analog ingång starta om enheten.
Nästa register 22—30 används inte. De är skrivskyddade.
Holding register 31 åsidosätter utgångsspänningsvärdet i Modbus-läge när
åsidosättning av utdata är aktiverat. Inställningen för överstyrningsvärde beror inte på
de andra inställningarna förutom på valet av direktstart eller mjukstart. Standardvärdet
är '0' (VAC). Registervärdet kan variera mellan 30100 (30—100 % Us). Det kan ock
vara "0" (0 % Us).
Nästa holding register 32—40 används inte. De är skrivskyddade.
TRANSPORT OCH LAGRING
Undvik vibrationer och extrema förhållanden. Förvara i originalförpackning.
GARANTI OCH BEGRÄNSNINGAR
Två år från leveransdatum mot tillverkningsfel. Ändringar eller omvandlingar av
produkten efter publiceringsdatumet fritar tillverkaren från allt ansvar. Tillverkaren
ansvarar inte för tryckfel eller fel i ovanstående data.
UNDERHÅLL
Under normala förhållanden är denna produkt underhållsfri. Rengör med en torr
eller fuktig trasa om den är smutsig. Vid kraftig förorening, rengör med en icke
aggressiv produkt. Under dessa omständigheter bör enheten kopplas bort från
strömförsörjningen. Var uppmärksam på att inga vätskor kommer in i enheten.
Anslut den bara till elnätet igen när den är helt torr.