Victron energy MultiPlus 5k 100A 230V (firmware xxxx1xx) Bruksanvisning

Typ
Bruksanvisning
Manual
EN
Handl
eiding
NL
Manue
l
FR
Anleitung
DE
Manual
ES
Användarhandbok
SE
Appendix
MultiPlus (firmware xxxx1xx)
12 | 5000 | 200 - 100 | 230/240V
24 | 5000 | 120 - 100 | 230/240V
48 | 5000 | 70 - 100 | 230/240V
1
EN NL FR DE ES SE Appendix
1. SAFETY INSTRUCTIONS
In general
Please read the documentation supplied with this product first, so that you are familiar with the safety signs en directions before using
the product.
This product is designed and tested in accordance with international standards. The equipment should be used for the designated
application only.
WARNING: DANGER OF ELECTRICAL SHOCK
The product is used in combination with a permanent energy source (battery). Even if the equipment is switched off, a dangerous
electrical voltage can occur at the input and/or output terminals. Always switch the AC power off and disconnect the battery before
performing maintenance.
The product contains no internal user-serviceable parts. Do not remove the front panel and do not put the product into operation unless
all panels are fitted. All maintenance should be performed by qualified personnel.
Never use the product at sites where gas or dust explosions could occur. Refer to the specifications provided by the manufacturer of the
battery to ensure that the battery is suitable for use with this product. The battery manufacturer's safety instructions should always be
observed.
WARNING: do not lift heavy objects unassisted.
Installation
Read the installation instructions before commencing installation activities.
This product is a safety class I device (supplied with a ground terminal for safety purposes). Its AC input and/or output terminals
must be provided with uninterruptible grounding for safety purposes. An additional grounding point is located on the outside
of the product. If it can be assumed that the grounding protection is damaged, the product should be taken out of operation and
prevented from accidentally being put into operation again; contact qualified maintenance personnel.
Ensure that the connection cables are provided with fuses and circuit breakers. Never replace a protective device by a component of a
different type. Refer to the manual for the correct part.
Check before switching the device on whether the available voltage source conforms to the configuration settings of the product as
described in the manual.
Ensure that the equipment is used under the correct operating conditions. Never operate it in a wet or dusty environment.
Ensure that there is always sufficient free space around the product for ventilation, and that ventilation openings are not blocked.
Install the product in a heatproof environment. Ensure therefore that there are no chemicals, plastic parts, curtains or other textiles, etc.
in the immediate vicinity of the equipment.
Transport and storage
On storage or transport of the product, ensure that the mains supply and battery leads are disconnected.
No liability can be accepted for damage in transit if the equipment is not transported in its original packaging.
Store the product in a dry environment; the storage temperature should range from 20°C to 60°C.
Refer to the battery manufacturer's manual for information on transport, storage, charging, recharging and disposal of the battery.
2
2. DESCRIPTION
2.1 In general
The basis of the MultiPlus is an extremely powerful sine inverter, battery charger and automatic switch in a compact casing.
The MultiPlus features the following additional, often unique characteristics:
Automatic and uninterruptible switching
In the event of a supply failure or when the generating set is switched off, the MultiPlus will switch over to inverter operation and take
over the supply of the connected devices. This is done so quickly that operation of computers and other electronic devices is not
disturbed (Uninterruptible Power Supply or UPS functionality). This makes the MultiPlus highly suitable as an emergency power system
in industrial and telecommunication applications. The maximum alternating current that can be switched is 16A or 50A, depending on
model.
Auxiliary AC output
Besides the usual uninterruptable output, an auxiliary output is available that disconnects its load in the event of battery operation.
Example: an electric boiler that is allowed to operate only if the genset is running or shore power is available.
Virtually unlimited power thanks to parallel operation
Up to 6 MultiPlus units can operate in parallel. Six units 48/5000/70, for example, will provide 24kW / 30kVA output power and 420
Amps charging capacity.
Three phase capability
Three units can be configured for three-phase output. But that’s not all: up to 6 sets of three units can be parallel connected to provide
72kW / 90kVA inverter power and more than 1200A charging capacity.
PowerControl maximum use of limited shore current
The MultiPlus can supply a huge charging current. This implies heavy loading of the shore connection or generator set. Therefore a
maximum current can be set. The MultiPlus then takes other power users into account, and only uses 'surplus' current for charging
purposes.
PowerAssist Extended use of your generator and shore current: the MultiPlus “co-supply” feature
This feature takes the principle of PowerControl to a further dimension allowing the MultiPlus to supplement the capacity of the
alternative source. Where peak power is so often required only for a limited period, the MultiPlus will make sure that insufficient shore or
generator power is immediately compensated for by power from the battery. When the load reduces, the spare power is used to
recharge the battery.
This unique feature offers a definitive solution for the ‘shore current problem’:high power electric tools, dish washers,
washing machines, electric cooking etc. can all run on 16A shore current, or even less. In addition, a smaller generator can be
installed.
Solar energy
The MultiPlus is extremely suitable for solar energy applications. It can be used in autonomous systems as well as grid connected
systems.
Autonomous operation when the grid fails
Houses or buildings with solar panels or a combined micro-scale heating and power plant or other sustainable energy sources have a
potential autonomous energy supply which can be used for powering essential equipment (central heating pumps, refrigerators, deep
freeze units, Internet connections, etc.) during a power failure. A problem is however that grid connected sustainable energy sources
drop out as soon as the grid fails. With a MultiPlus and batteries, this problem can be solved in a simple manner: the MultiPlus can
replace the grid during a power failure. When the sustainable energy sources produce more power than needed, the MultiPlus will
use the surplus to charge the batteries; in the event of a shortfall, the MultiPlus will supply additional power from the battery.
Programmable relay
The MultiPlus is equipped with a programmable relay that by default is set as an alarm relay. The relay can be programmed for all kinds
of other applications however, for example as a starter relay for a generator.
Programmable with DIP switches, VE.Net panel or personal computer
The MultiPlus is supplied ready for use. Three features are available for changing certain settings if desired:
- The most important settings (including parallel operation of up to three devices and 3-phase operation) can be changed in a very
simple manner, using DIP switches.
- All settings, with exception of the multi-functional relay, can be changed with a VE.Net panel.
- All settings can be changed with a PC and free of charge software, downloadable from our website www.victronenergy.com
3
EN NL FR DE ES SE Appendix
2.2 Battery charger
Adaptive 4-stage charging characteristics: bulk absorption float storage
The microprocessor-driven adaptive battery management system can be adjusted for various types of batteries. The adaptive function
automatically adapts the charging process to battery use.
The right amount of charge: variable absorption time
In the event of slight battery discharge, absorption is kept short to prevent overcharging and excessive gas formation. After deep
discharging, the absorption time is automatically extended in order to fully charge the battery.
Preventing damage due to excessive gassing: the BatterySafe mode
If, in order to quickly charge a battery, a high charge current in combination with a high absorption voltage has been chosen, damage
due to excessive gassing will be prevented by automatically limiting the rate of voltage increase once the gassing voltage has been
reached.
Less maintenance and aging when the battery is not in use: the Storage mode
The Storage mode kicks in whenever the battery has not been subjected to discharge during 24 hours. In the Storage mode float
voltage is reduced to 2,2V/cell (13,2V for 12V battery) to minimise gassing and corrosion of the positive plates. Once a week the
voltage is raised back to the absorption level to ‘equalize’ the battery. This feature prevents stratification of the electrolyte and
sulphation, a major cause of early battery failure.
Two DC outputs for charging two batteries
The main DC terminal can supply the full output current. The second output, intended for charging a starter battery, is limited to 4A and
has a slightly lower output voltage.
Increasing service life of the battery: temperature compensation
The temperature sensor (supplied with the product) serves to reduce charging voltage when battery temperature rises. This is
particularly important for maintenance-free batteries, which could otherwise dry out by overcharging.
Battery voltage sense: the correct charge voltage
Voltage loss due to cable resistance can be compensated by using the voltage sense facility to measure voltage directly on the DC bus
or on the battery terminals.
More on batteries and charging
Our book ‘Energy Unlimited’ offers further information on batteries and battery charging, and is available free of charge on our website
(see www.victronenergy.com -> Support & Downloads’ -> General Technical Information). For more information on adaptive charging,
please also refer to the General Technical Information our website.
2.3 Self consumption solar energy storage systems
When the Multi/Quattro is used in a configuration in which it will feed back energy to the grid it is required to enable grid code
compliance by selecting the grid code country setting with the VEConfigure tool.
This way the Multi/Quattro can comply to the local rules.
Once set, a password will be required to disable grid code compliance or change grid code related parameters.
If the local grid code is not supported by the Multi/Quattro an external certified interface device should be used to connect the
Multi/Quattro to the grid.
4
3. OPERATION
3.1 On/Off/Charger Only Switch
When switched to "on", the product is fully functional. The inverter will come into operation and the LED "inverter on" will light up.
An AC voltage connected to the "AC in" terminal will be switched through to the "AC out" terminal, if within specifications. The inverter
will switch off, the "mains on" LED will light up and the charger commences charging. The "bulk", "absorption" or "float" LEDs will light
up, depending on the charger mode.
If the voltage at the "AC-in" terminal is rejected, the inverter will switch on.
When the switch is switched to "charger only", only the battery charger of the MultiPlus unit will operate (if mains voltage is present). In
this mode input voltage also is switched through to the "AC out" terminal.
NOTE: When only the charger function is required, ensure that the switch is switched to "charger only". This prevents the inverter from
being switched on if the mains voltage is lost, thus preventing your batteries from running flat.
3.2 Remote control
Remote control is possible with a 3-way switch or with a Multi Control panel.
The Multi Control panel has a simple rotary knob with which the maximum current of the AC input can be set: see PowerControl and
PowerAssist in Section 2.
3.3 Equalisation and forced absorption
3.3.1 Equalisation
Traction batteries require regular additional charging. In the equalisation mode, the MultiPlus will charge with increased voltage for one
hour (1V above the absorption voltage for a 12V battery, 2V for a 24V battery). The charging current is then limited to 1/4 of the set
value. The “bulk” and “absorption” LEDs flash intermittently.
Equalisation mode supplies a higher charging voltage than most DC consuming
devices can cope with. These devices must be disconnected before additional
charging takes place.
3.3.2 Forced absorption
Under certain circumstances, it can be desirable to charge the battery for a fixed time at absorption voltage level. In Forced Absorption
mode, the MultiPlus will charge at the normal absorption voltage level during the set maximum absorption time. The “absorption” LED
lights.
3.3.3 Activating equalisation or forced absorption
The MultiPlus can be put into both these states from the remote panel as well as with the front panel switch, provided that all switches
(front, remote and panel) are set to “on” and no switches are set to “charger only”.
In order to put the MultiPlus in this state, the procedure below should be followed.
If the switch is not in the required position after following this procedure, it can be switched over quickly once. This will not change the
charging state.
NOTE: Switching from “on” to “charger only” and back, as described below, must be done quickly. The switch must be toggled such that
the intermediate position is 'skipped', as it were. If the switch remains in the “off” position even for a short time, the device may be turned
off. In that case, the procedure must be restarted at step 1. A certain degree of familiarisation is required when using the front switch on
the Compact in particular. When using the remote panel, this is less critical.
Procedure:
1. Check whether all switches (i.e. front switch, remote switch or remote panel switch if present) are in the “on” position.
2. Activating equalisation or forced absorption is only meaningful if the normal charging cycle is completed (charger is in 'Float').
3. To activate:
a. Switch rapidly from “on” to “charger only” and leave the switch in this position for ½ to 2 seconds.
b. Switch rapidly back from “charger only” to “on” and leave the switch in this position for ½ to 2 seconds.
c. Switch once more rapidly from “on” to “charger only” and leave the switch in this position.
4. On the MultiPlus (and, if connected, on the Multi Control panel) the three LEDs “Bulk”, “Absorption” and “Float” will now flash 5 times.
5. Subsequently, the LEDs “Bulk”, “Absorption” and “Float” will each light during 2 seconds.
a. If the switch is set to “on” while the “Bulk” LED lights, the charger will switch to equalisation.
b. If the switch is set to “on” while the “Absorption” LED lights, the charger will switch to forced absorption.
c. If the switch is set to “on” after the three LED sequence has finished, the charger will switch to “Float”.
d. If the switch is has not been moved, the MultiPlus will remain in ‘charger only’ mode and switch to “Float”.
5
EN NL FR DE ES SE Appendix
3.4 LED Indications
LED off
LED flashes
LED illuminated
Inverter
inverter
The inverter is on and supplies
power to the load.
mains on
on
inverter on
Bulk
overload
off
Absorption
low battery
charger
only
Float
temperature
Charger
inverter
The nominal output of the inverter is
exceeded. The “overload” LED
flashes
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
inverter
The inverter is switched off due to
overload or short circuit.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
The battery is almost fully
exhausted.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
inverter
The inverter has switched off due to
low battery voltage.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
inverter
The internal temperature is reaching
a critical level.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
6
Charger
inverter
The inverter has switched off due to
the electronics temperature being
too high.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
inverter
-If the LEDs are flashing alternately,
the battery is nearly exhausted and
the nominal output is exceeded.
-If "overload" and "low battery" flash
simultaneously, the ripple voltage
on the battery terminals is too high.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
inverter
The inverter switched off due to
excess ripple voltage on the battery
terminals.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Battery Charger
Charger
inverter
The AC input voltage is switched
through and the charger operates in
bulk mode.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
inverter
The mains voltage is switched
through and the charger is on.
The set absorption voltage,
however, has not yet been reached.
(BatterySafe mode)
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
inverter
The mains voltage is switched
through and the charger operates in
absorption mode.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
7
EN NL FR DE ES SE Appendix
Charger
inverter
The mains voltage is switched
through and the charger operates in
float mode.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
inverter
The mains voltage is switched
through and the charger operates in
equalize mode.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Special Indications
PowerControl
charger
inverter
The AC input is switched through.
The AC output current is equal to
the preset maximum input current.
The charge current is reduced to 0.
mains on
on
inverter on
bulk
overload
off
absorption
low battery
charger
only
float
temperature
Power Assist
charger
inverter
The AC input is switched through
but the load requires more current
than the preset maximum input
current. The inverter is switched on
to supply the required additional
current.
mains on
on
inverter on
bulk
overload
off
absorption
low battery
charger
only
float
temperature
8
4. INSTALLATION
This product may only be installed by a qualified electrical engineer.
4.1 Location
The product must be installed in a dry and well-ventilated area, as close as possible to the batteries. There should be a clear space of at
least 10 cm around the appliance for cooling.
Excessively high ambient temperature will result in the following:
- Reduced service life.
- Reduced charging current.
- Reduced peak capacity, or shutdown of the inverter.
- Never position the appliance directly above the batteries.
The MultiPlus is suitable for wall mounting. For mounting purposes, a hook and two holes are provided at the back of the casing (see
appendix G). The device can be fitted either horizontally or vertically. For optimal cooling, vertical fitting is preferred.
The interior of the product must remain accessible after installation.
Try and keep the distance between the product and the battery to a minimum in order to minimize cable voltage losses.
For safety purposes, this product should be installed in a heat-resistant
environment. You should prevent the presence of e.g. chemicals, synthetic
components, curtains or other textiles, etc., in the immediate vicinity.
4.2 Connection of battery cables
In order to utilize the full capacity of the product, batteries with sufficient capacity and battery cables with sufficient cross section should
be used. See table.
12/5000/200
24/5000/120
48/5000/70
Recommended battery capacity (Ah)
8004200
4001400
200800
Recommended DC fuse 750A 400A 200A
Recommended cross section (mm
2
)
per + and - connection terminal
0 5 m 2x 90 mm
2
2x 50 mm
2
1x 70 mm
2
5 10 m 2x 90 mm
2
2x 70 mm
2
* ‘2x’ means two positive and two negative cables.
Remark: Internal resistance is the important factor when working with low capacity batteries. Please consult your supplier or the relevant
sections of our book “Energy Unlimited”, downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
- Undo the four screws at the front of the enclosure and remove the front panel.
- Connect the battery cables: see Appendix A.
- Tighten the nuts well for minimal contact resistance.
9
EN NL FR DE ES SE Appendix
4.3 Connection of the AC cabling
The MultiPlus is a safety class I product (supplied with a ground terminal for
safety purposes). Its AC input and/or output terminals and/or
grounding point on the outside of the product must be provided with
an uninterruptible grounding point for safety purposes.
The MultiPlus is provided with a ground relay (relay H, see appendix B) that
automatically connects the Neutral output to the chassis if no external
AC supply is available. If an external AC supply is provided, the ground
relay H will open before the input safety relay closes. This ensures the
correct operation of an earth leakage circuit breaker that is connected to
the output.
- In a fixed installation, an uninterruptable grounding can be secured by
means of the grounding wire of the AC input. Otherwise the casing must be
grounded.
- In a mobile installation (for example, with a shore current plug),
interrupting the shore connection will simultaneously disconnect the
grounding connection. In that case, the casing must be connected to the
chassis (of the vehicle) or to the hull or grounding plate (of the boat).
- In case of a boat, direct connection to the shore ground is not
recommended because of potential galvanic corrosion. The solution to this
is using an isolation transformer.
The terminal blocks can be found on the printed circuit board, see Appendix A. The shore or mains cable must be connected to the
MultiPlus with the aid of a three-wire cable.
- AC-in
The AC input cable can be connected to the terminal block “ACin”.
From left to right: “PE” (earth), “N” (neutral) and “L” (phase).
The AC input must be protected by a fuse or magnetic circuit breaker rated at 100A or less, and cable cross-section must be
sized accordingly. If the input AC supply is rated at a lower value, the fuse or magnetic circuit breaker should be down sized
accordingly.
- AC-out-1 (see appendix A)
The AC output cable can be connected directly to the terminal block "AC-out".
With its PowerAssist feature the MultiPlus can add up to 5kVA (that is 5000 / 230 = 22A) to the output during periods of peak power
requirement. Together with a maximum input current of 100A this means that the output can supply up to 100 + 22 = 122A.
An earth leakage circuit breaker and a fuse or circuit breaker rated to support the expected load must be included in series
with the output, and cable cross-section must be sized accordingly. The maximum rating of the fuse or circuit breaker is 122A.
- AC-out-2 (see appendix A)
A second output is available that disconnects its load in the event of battery operation. On these terminals, equipment is connected that
may only operate if AC voltage is available on AC-in, e.g. an electric boiler or an air conditioner. The load on AC-out-2 is
disconnected immediately when the MultiPlus switches to battery operation. After AC power becomes available on AC-in, the load on
AC-out-2 will be reconnected with a delay of approximately 2 minutes. This to allow a genset to stabilise.
AC-out-2 can support loads of up to 50A. An earth leakage circuit breaker and fuse rated at max. 50A must be connected in series with
AC-out-2.
Note: Loads connected to AC-out-2 will be taken into account in the PowerControl / PowerAssist current limit setting. Loads directly
connected to the AC supply will not be included in the PowerControl / PowerAssist current limit setting.
10
4.4 Optional Connections
A number of optional connections are possible:
4.4.1 Second Battery
The MultiPlus has a connection for charging a starter battery. For connection see Appendix A.
4.4.2 Voltage Sense
Two sense wires may be connected to compensate possible battery cable losses during charging. Use wires of at least 0.75mm
2
. For
connection see Appendix 0.
4.4.3 Temperature Sensor
The temperature sensor supplied with the product may be used for temperature-compensated charging (see Appendix A). The sensor is
isolated and must be mounted on the batteries minus pole.
4.4.4 Remote Control
The product can be remotely controlled in two ways.
- With an external switch (connection terminal L, see appendix A). Operates only if the switch on the MultiPlus unit is set to “on”.
- With a Multi Control panel (connected to one of the two RJ48 sockets B, see appendix A). Operates only if the switch on the MultiPlus
is set to “on”.
Only one remote control can be connected, i.e. either a switch or a remote control panel.
4.4.5. Programmable relay
The MultiPlus is equipped with a programmable relay that by default is set as an alarm relay. The relay can be programmed for all kinds
of other applications however, for example to start a generator (VEConfigure software needed).
4.4.6 Auxiliary AC output (AC-out-2)
Besides the usual uninterruptable output, a second output (AC-out-2) is available that disconnects its load in the event of battery
operation. Example: an electric boiler or air conditioner that is allowed to operate only if the genset is running or shore power is
available.
In case of battery operation, AC-out-2 is switched off immediately. After the AC supply has become available, AC-out-2 is reconnected
with a delay of 2 minutes, this to allow a genset to stabilise prior to connecting a heavy load.
4.4.7 Parallel Connection
The MultiPlus can be connected in parallel with several identical devices. To this end, a connection is established between the devices
by means of standard RJ45 UTP cables. The system (one or more MultiPlus units plus optional control panel) will require subsequent
configuration (see Section 5).
In the event of connecting MultiPlus units in parallel, the following requirements must be met:
- A maximum of six units connected in parallel (per phase).
- Only identical devices may be connected in parallel.
- The DC connection cables to the devices must be of equal length and cross-section.
- The AC input cables to each unit as well as the AC output cables to each unit must also be of equal length and cross-section (length to
AC input may be different from length to AC output).
Additionally the AC input and output cables to each unit should have a minimum resistance of 4 milliohm (in oder to prevent excessive
AC current unbalance between parallel units due to differeces of terminal and relay contact resistance).
As a result the minimum length of the AC input and output cables is as follows:
Cable cross section 6 mm² (9 AWG): min. length 0,7 meter
Cable cross section 10 mm² (7 AWG): min. length 1,2 meter
- If a positive and a negative DC distribution point is used, the cross-section of the connection between the batteries and the DC
distribution point must at least equal the sum of the required cross-sections of the connections between the distribution point and the
MultiPlus units.
- Place the MultiPlus units close to each other, but allow at least 10 cm for ventilation purposes under, above and beside the units.
- UTP cables must be connected directly from one unit to the other (and to the remote panel). Connection/splitter boxes are not
permitted.
- A battery-temperature sensor need only be connected to one unit in the system. If the temperature of several batteries is to be
measured, you can also connect the sensors of other MultiPlus units in the system (with a maximum of one sensor per MultiPlus).
Temperature compensation during battery charging responds to the sensor indicating the highest temperature.
- Voltage sensing must be connected to the master (see Section 5.5.1.4).
- If more than three units are connected in parallel in one system, a dongle is required (see Section 5).
- Only one remote control means (panel or switch) can be connected to the system.
4.4.8 Three-phase operation
The MultiPlus can also be used in 3-phase wye (Y) configuration. To this end, a connection between the devices is made by means of
standard RJ45 UTP cables (the same as for parallel operation). The system (MultPlus units plus an optional control panel) will require
subsequently configuration (see Section 5).
Pre-requisites: see Section 4.4.7.
Note: the MultiPlus is not suitable for 3-phase delta (Δ) configuration.
11
EN NL FR DE ES SE Appendix
5. CONFIGURATION
Settings may only be changed by a qualified electrical engineer.
Read the instructions thoroughly before implementing changes.
During setting of the charger, the AC input must be removed.
5.1 Standard settings: ready for use
On delivery, the MultiPlus is set to standard factory values. In general, these settings are suitable for single-unit operation.
Warning: Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard MultiPlus factory settings
Inverter frequency 50 Hz
Input frequency range 45 - 65 Hz
Input voltage range 180 - 265 VAC
Inverter voltage 230 VAC
Stand-alone / parallel / 3-phase stand-alone
AES (Automatic Economy Switch) off
Ground relay on
Charger on/ off on
Battery charge curve four-stage adaptive with BatterySafe mode
Charging current 75% of the maximum charging current
Battery type Victron Gel Deep Discharge (also suitable for Victron AGM Deep Discharge)
Automatic equalisation charging off
Absorption voltage 14.4 / 28.8 / 57.6 V
Absorption time up to 8 hours (depending on bulk time)
Float voltage 13.8 / 27.6 / 55.2 V
Storage voltage 13.2 / 26.4 / 52.8V (not adjustable)
Repeated absorption time 1 hour
Absorption repeat interval 7 days
Bulk protection on
AC input current limit 50A (= adjustable current limit for PowerControl and PowerAssist functions)
UPS feature on
Dynamic current limiter off
WeakAC off
BoostFactor 2
Auxiliary output 25A
PowerAssist on
Programmable relay alarm function
5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the software
configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50Hz; 60Hz
Input frequency range
Input frequency range accepted by the MultiPlus. The MultiPlus synchronises within this range with the AC input frequency. The output
frequency is then equal to the input frequency.
Adjustability: 45 65 Hz; 45 55 Hz; 55 65 Hz
Input voltage range
Voltage range accepted by the MultiPlus. The MultiPlus synchronises within this range with the AC input voltage. The output voltage is
then equal to the input voltage.
Adjustability: Lower limit: 180 - 230V
Upper limit: 230 - 270V
Note: the standard lower limit setting of 180V is intended for stand alone operation only. In case of high power parallel or 3
phase systems, the lower input voltage limit stting must be increased to 210V or more.
Inverter voltage
Output voltage of the MultiPlus in battery operation.
Adjustability: 210 245V
12
Stand-alone / parallel operation / 2-3 phase setting
Using several devices, it is possible to:
- increase total inverter power (several devices in parallel)
- create a split-phase system by stacking (only for MultiPlus units with 120V output voltage)
- create a split-phase system with a separate autotransformer: see VE autotransformer datasheet and manual
- create a 3-phase system.
The standard product settings are for standalone operation. For parallel, three phase or split phase operation see section 4.6.6 and
4.6.7
AES (Automatic Economy Switch)
If this setting is turned ‘on’, the power consumption in no-load operation and with low loads is decreased by approx. 20%, by slightly
'narrowing' the sinusoidal voltage. Applicable in stand-alone configuration only.
Search Mode
Instead of the AES mode, the search mode can also be chosen (with help of VEConfigure only).
If search mode is ‘on’, the power consumption in no-load operation is decreased by approx. 70%. In this mode the MultiPlus, when
operating in inverter mode, is switched off in case of no load or very low load, and switches on every two seconds for a short period. If
the output current exceeds a set level, the inverter will continue to operate. If not, the inverter will shut down again.
The Search Mode “shut down” and “remain on” load levels can be set with VEConfigure.
The standard settings are:
Shut down: 40 Watt (linear load)
Turn on: 100 Watt (linear load)
Not adjustable with DIP switches. Applicable in stand-alone configuration only.
Ground relay (see appendix B)
With this relay (E), the neutral conductor of the AC output is grounded to the chassis when the back feed safety relay is open. This
ensures the correct operation of earth leakage circuit breakers in the output.
- If a non-grounded output is required during inverter operation, this function must be turned off by shifting switch N (see appendix A).
- If required an external ground relay can be connected (for a split-phase system with a separate autotransformer). Shift switch N (see
appendix A).
Charging characteristics
The standard setting is ‘Four-stage adaptive with BatterySafe mode’. See Section 2 for a description.
This is the best charging characteristic. See the help files in the software configuration programs for other features.
‘Fixed’ mode can be selected with DIP switches.
Battery type
The standard setting is the most suitable for Victron Gel Deep Discharge, Gel Exide A200, and tubular plate stationary batteries (OPzS).
This setting can also be used for many other batteries: e.g. Victron AGM Deep Discharge and other AGM batteries, and many types of
flat-plate open batteries. Four charging voltages can be set with DIP switches.
Automatic equalisation charging
This setting is intended for tubular plate traction batteries. During absorption the voltage limit increases to 2,83V/cell (34V for a 24V
battery) once the charge current has tapered down to less than 10% of the set maximum current.
Not adjustable with DIP switches.
See ’tubular plate traction battery charge curve’ in VEConfigure.
Absorption time
The absortion time depends on the bulk time (adaptive charge curve), so that the battery is optimally charged. If the ‘fixed’ charging
characteristic is selected, the absorption time is fixed. For most batteries, a maximum absorption time of eight hours is suitable. If an
extra high absorption voltage is selected for rapid charging (only possible for open, flooded batteries!), four hours is preferable. With DIP
switches, a time of eight or four hours can be set. For the adaptive charge curve, this determines the maximum absorption time.
Storage voltage, Repeated Absorption Time, Absorption Repeat Interval
See Section 2. Not adjustable with DIP switches.
Bulk Protection
When this setting is ‘on’, the bulk charging time is limited to 10 hours. A longer charging time could indicate a system error (e.g. a
battery cell short-circuit). Not adjustable with DIP switches.
AC input current limit
These are the current limit settings for which PowerControl and PowerAssist come into operation.
PowerAssit setting range:
From 6,3A to 50A.
Factory setting: the maximum value (50A).
See Section 2, the book 'Energy Unlimited', or the many descriptions of the unique PowerAssist feature on our website
www.victronenergy.com.
13
EN NL FR DE ES SE Appendix
UPS feature
If this setting is ‘on’ and AC on the input fails, the MultiPlus switches to inverter operation practically without interruption. The MultiPlus
can therefore be used as an Uninterruptible Power Supply (UPS) for sensitive equipment such as computers or communication
systems.
The output voltage of some small generator sets is too unstable and distorted for using this setting the MultiPlus would continually
switch to inverter operation. For this reason, the setting can be turned off. The MultiPlus will then respond less quickly to AC input
voltage deviations. The switchover time to inverter operation is consequently slightly longer, but most equipment (most computers,
clocks or household equipment) is not adversely impacted.
Recommendation: Turn the UPS feature off if the MultiPlus fails to synchronise, or continually switches back to inverter operation.
Dynamic current limiter
Intended for generators, the AC voltage being generated by means of a static inverter (so-called ‘inverter’ generators). In these
generators, rpm is down-controlled if the load is low: this reduces noise, fuel consumption and pollution. A disadvantage is that the
output voltage will drop severely or even completely fail in the event of a sudden load increase. More load can only be supplied after the
engine is up to speed.
If this setting is ‘on’, the MultiPlus will start supplying extra power at a low generator output level and gradually allow the generator to
supply more, until the set current limit is reached. This allows the generator engine to get up to speed.
This setting is also often used for ‘classical’ generators that respond slowly to sudden load variation.
WeakAC
Strong distortion of the input voltage can result in the charger hardly operating or not operating at all. If WeakAC is set, the charger will
also accept a strongly distorted voltage, at the cost of greater distortion of the input current.
Recommendation: Turn WeakAC on if the charger is hardly charging or not charging at all (which is quite rare!). Also turn on the
dynamic current limiter simultaneously, and reduce the maximum charging current to prevent overloading the generator if necessary.
Note: when WeakAC is on, the maximum charge current is reduced by approximately 20%.
Not adjustable with DIP switches.
BoostFactor
Change this setting only after consulting with Victron Energy or with an engineer trained by Victron Energy!
Not adjustable with DIP switches.
Auxiliary AC output (AC-out-2)
Besides the uninterruptable output, a second output (AC-out-2) is available that disconnects its load in the event of battery operation.
Example: an electric boiler or air conditioner that is allowed to operate only if the genset is running or shore power is available.
In case of battery operation, AC-out-2 is switched off immediately. After the AC supply has become available, AC-out-2 is reconnected
with a delay of 2 minutes, this to allow a genset to stabilise prior to connecting a heavy load.
Three programmable relays
The MultiPlus is equipped with 3 programmable relays. The relays can be programmed for all kinds of other applications, for example as
a starter relay for a generating set. The default setting of the relay in postion I (see appendix A, upper right corner) is ‘alarm’.
Not adjustable with DIP switches.
Two programmable analog/digital input/output ports
The MultiPlus is equipped with 2 analog/digital input/output ports.
These ports can be used for several purposes. One application is communication with the BMS of a lithium-ion battery.
Not adjustable with DIP switches.
Frequency shift
When solar inverters are connected to the output of a Multi or Quattro, the excess solar energy is used to recharge the batteries. Once
the absorption voltage is reached, the Multi or Quattro will shut down the solar inverter by shifting the output frequency 1Hz (from 50Hz
to 51Hz for example). Once battery voltage has dropped slightly, the frequency returns to normal and the solar inverters will restart.
Not adjustable with DIP switches.
VEConfigure software
With VEConfigure software the relay can also be programmed for other purposes, for example to provide a generator starting signal.
With VEConfigure, several other special application modes of operation can be programmed.
Example: A house or an office connected to the public mains, fitted with solar panels with energy storage in batteries.
The batteries are used to prevent return delivery to the mains. During the day, redundant solar energy is stored in
batteries. This energy is used in the evenings and at night. An energy shortfall is compensated by the mains. The
MultiPlus converts the battery DC voltage to AC. The power is always less than or equal to the power consumption, so
that return delivery to the mains does not occur. In the event of mains failure, the MultiPlus isolates the premises from
the mains, which become autonomous (self-sufficient). In this way, a solar energy installation or a combined micro-scale
heating and power plant can be economically used in areas with an unreliable mains supply and/or financially
unfavourable energy-return conditions.
14
5.3 Configuration by computer
All settings can be changed by means of a computer or with a VE.Net panel (except for the multi-functional relay and the VirtualSwitch
when using VE.Net).
The most common settings (including parallel and 3-phase operation) can be changed by means of DIP switches (see Section 5.5).
For changing settings with the computer, the following is required:
VEConfigure3 software: can be downloaded free of charge at www.victronenergy.com.
A MK3-USB (VE.Bus to USB) interface.
Alternatively, the Interface MK2.2b (VE.Bus to RS232) can be used (RJ45 UTP cable needed).
5.3.1 VE.Bus Quick Configure Setup
VE.Bus Quick Configure Setup is a software program with which systems with a maximum of three MultiPlus units (parallel or three
phase operation) can be configured in a simple manner.
The software can be downloaded free of charge at www.victronenergy.com.
5.3.2 VE.Bus System Configurator
For configuring advanced applications and/or systems with four or more MultiPlus units, VE.Bus System Configurator software must
be used. The software can be downloaded free of charge at www.victronenergy.com .
5.4 Configuration with a VE.Net panel
To this end, a VE.Net panel and the VE.Net to VE.Bus converter is required.
With VE.Net all parameters are accessible, with the exception of the multi-functional relay and the VirtualSwitch.
15
EN NL FR DE ES SE Appendix
5.5 Configuration with DIP switches
A number of settings can be changed using DIP switches (see appendix A, position M).
This is done as follows:
Turn the MultiPlus on, preferably unloaded en without AC voltage on the inputs. The Multi will then operate in inverter mode.
Step 1: Setting the DIP switches for:
- the required current limitation of the AC input.
- AES (Automatic Economy Switch)
- limitation of the charging current.
- selection of stand-alone, parallel or 3-phase operation.
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of the DIP
switches, see appendix A, position K). You can now re-use the DIP switches to apply the remaining settings (step 2).
Step 2: other settings
To store the settings after the required values have been set: press the 'Down' button for 2 seconds (lower button to the right of the DIP
switches). You can now leave the DIP switches in the selected positions, so that the ’other settings’ can always be recovered.
Remarks:
- The DIP switch functions are described in 'top to bottom' order. Since the uppermost DIP switch has the highest number (8),
descriptions start with the switch numbered 8.
- In parallel mode or 3-phase mode, not all devices require all settings to be made (see section 5.5.1.4).
For parallel or 3-phase mode, read the whole setting procedure and make a note of the required DIP switch settings before actually
implementing them.
5.5.1 Step 1
5.5.1.1 Current limitation AC input (default: 50A)
If the current demand (Multi load + battery charger) threatens to exceed the set current, the MultiPlus will first reduce its charging
current (PowerControl), and subsequently supply additional power from the battery (PowerAssist), if needed.
The AC input current limit can be set to eight different values by means of DIP switches.
With a Multi Control Panel, a variable current limit can be set for the AC input.
Procedure
The AC input current limit can be set using DIP switches ds8, ds7 and ds6 (default setting: 50A).
Procedure: set the DIP switches to the required value:
ds8 ds7 ds6
off off off = 6,3A (1.4kVA at 230V)
off off on = 10A (2.3kVA at 230V)
off on off = 12A (2.8kVA at 230V)
off on on = 16A (3.7kVA at 230V)
on off off = 20A (4.6kVA at 230V)
on off on = 25A (5.7kVA at 230V)
on on off = 30A (6.9kVA at 230V)
on on on = 50A (11.5kVA at 230V)
Remark: Manufacturer-specified continuous power ratings for small generators are sometimes inclined to be rather
optimistic. In that case, the current limit should be set to a much lower value than would otherwise be required on
the basis of manufacturer-specified data.
5.5.1.2 AES (Automatic Economy Switch)
Procedure: set ds5 to the required value:
ds5
off = AES off
on = AES on
16
5.5.1.3 Battery charge current limitation (default setting 75%)
For maximum battery life, a charge current of 10% to 20% of the capacity in Ah should be applied.
Example: optimal charge current of a 24V/500Ah battery bank: 50A to 100A.
The temperature sensor supplied automatically adjusts the charge voltage to the battery temperature.
If faster charging and a subsequent higher current is required:
- The temperature sensor supplied should always be fitted, since fast charging can lead to a considerable temperature rise of the battery
bank. The charge voltage will be adapted to the higher temperature (i.e. lowered) by means of the temperature sensor.
- The bulk charge time will sometimes be so short that a fixed absorption time would be more satisfactory (‘fixed’ absorption time, see
ds5, step 2).
Procedure
The battery charge current can be set in four steps, using DIP switches ds4 and ds3 (default setting: 75%).
ds4 ds3
off off = 25%
off on = 50%
on off = 75%
on on = 100%
Note: when WeakAC is on, the maximum charge current is reduced from 100% to approximately 80%.
5.5.1.4 Stand-alone, parallel and 3-phase operation
Using DIP switches ds2 and ds1, three system configurations can be selected.
NOTE:
All units in a parallel or three phase system must be connected to the same battery. The DC and the AC cabling of all
units must be of the same length and cross section.
When configuring a parallel or 3-phase system, all related devices should be interconnected using RJ45 UTP cables (see
appendix C, D). All devices must be turned on. They will subsequently return an error code (see Section 7), since they have
been integrated into a system and still are configured as ‘stand-alone’. This error message can safely be ignored.
Storing settings (by pressing the ‘Up’ button (step 1) and later on the ‘Down’ button (step 2) for 2 seconds) should be done
on one device only. This device is the ‘master’ in a parallel system or the ‘leader’ (L1) in a 3-phase system.
In a parallel system, the step-1 setting of DIP switches ds8 to ds3 need to be done on the master only. The slaves will follow
the master with regard to these settings (hence the master/slave relationship).
In a 3-phase system, a number of settings are required for the other devices, i.e. the followers (for phases L2 and L3).
(The followers, therefore, do not follow the leader for all settings, hence the leader/follower terminology).
A change in the setting ‘stand-alone / parallel / 3-phase’ is only activated after the setting has been stored (by pressing the
‘UP’ button for 2 seconds) and after all devices have been turned off and then on again. In order to start up a VE.Bus system
correctly, all devices should therefore be turned off after the settings have been stored. They can then be turned on in any
order. The system will not start until all devices have been turned on.
Note that only identical devices can be integrated in one system. Any attempt to use different models in one system will fail.
Such devices may possibly function correctly again only after individual reconfiguration for ‘stand-alone’ operation.
The combination ds2=on and ds1=on is not used.
17
EN NL FR DE ES SE Appendix
DIP switches ds2 and ds1 are reserved for the selection of stand-alone, parallel or
3-phase operation
Stand-alone operation
Step 1: Setting ds2 and ds1 for stand-alone operation
DS-8 AC input Set as desired
DS-7 AC input Set as desired
DS-6 AC input Set as desired
DS-5 AES Set as desired
DS-4 Charging current Set as desired
DS-3 Charging current Set as desired
DS-2 Stand-alone operation
off
DS-1 Stand-alone operation
off
Examples of DIP switch settings for stand-alone mode are given below.
Example 1 shows the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to ‘off’
and do not reflect the actual settings in the microprocessor).
Four examples of stand-alone settings:
DS-8 AC input
on
DS-7 AC input
on
DS-6 AC input
on
DS-5 AES
off
DS-4 Ch. current
on
DS-3 Ch. current
off
DS-2 St.-alone mode
off
DS-1 St.-alone mode
off
DS-8
on
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
DS-2
off
DS-1
off
DS-8
off
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
DS-2
off
DS-1
off
DS-8
on
DS-7
on
DS-6
off
DS-5
on
DS-4
off
DS-3
on
DS-2
off
DS-1
off
Step1, stand-alone
Example 1 (factory setting):
8, 7, 6 AC-in: 50A
5 AES: off
4, 3 Charging current: 75%
2, 1 Stand-alone mode
Step1, stand-alone
Example 2:
8, 7, 6 AC-in: 50A
5 AES: off
4, 3 Charge: 100%
2, 1 Stand-alone
Step1, stand-alone
Example 3:
8, 7, 6 AC-in: 16A
5 AES: off
4, 3 Charge: 100%
2, 1 Stand-alone
Step1, stand-alone
Example 4:
8, 7, 6 AC-in: 30A
5 AES: on
4, 3 Charge: 50%
2, 1 Stand-alone
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of the DIP
switches, see appendix A, position K). The overload and low-battery LED’s will flash to indicate acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe place.
You can now re-use the DIP switches to apply the remaining settings (step 2).
18
Parallel operation (appendix C)
Step 1: Setting ds2 and ds1 for parallel operation
Master
Slave 1
Slave 2 (optional)
DS-8 AC input Set
DS-7 AC input Set
DS-6 AC input Set
DS-5 AES na
DS-4 Ch. current Set
DS-3 Ch. current Set
DS-2 Master
off
DS-1 Master
on
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 1
off
DS-1 Slave 1
off
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 2
off
DS-1 Slave 2
on
The current settings (AC current limitation and charging current) are multiplied by the number of devices. However, the AC current limit
setting when using a remote panel will always correspond to the value indicated on the panel and is not multiplied by the number of
devices.
Example: 15kVA parallel system with 30A Multi Control Panel
- If an AC input current limit of 20A is set on the master and the system consists of three devices, then the effective system current limit
will be equal to 3 x 20 = 60A.
- If a 30A panel is connected to the master, the system current limit is adjustable to a maximum of 30A, regardless of the number of
devices.
- If the charging current on the master is set to 100% (70A for a MultiPlus 48/5000/70) and the system consists of three devices, then
the effective system charging current is equal to 3 x 70 = 210A.
The settings according to this example (15kVA parallel system with 30A Multi Control Panel) are as follows:
Master
Slave 1
Slave 2
DS-8 na (30A panel)
DS-7 na (30A panel)
DS-6 na (30A panel)
DS-5 AES na
DS-4 Ch. current 3x70A
on
DS-3 Ch. current 3x70A
on
DS-2 Master
off
DS-1 Master
on
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 1
off
DS-1 Slave 1
off
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 2
off
DS-1 Slave 2
on
To store the settings after the required values have been set: press the 'Up' button of the master for 2 seconds (upper button to the
right of the DIP switches, see appendix A, position K). The overload and low-battery LED’s will flash to indicate acceptance of the
settings.
We recommend making a note of the settings, and filing this information in a safe place.
You can now re-use the DIP switches to apply the remaining settings (step 2).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174

Victron energy MultiPlus 5k 100A 230V (firmware xxxx1xx) Bruksanvisning

Typ
Bruksanvisning