Munters M-AirCM-B1905 Bruksanvisning

Typ
Bruksanvisning
AirC-styrsystem
Bruksanvisning
M-AirCM-B1905
SVENSKA
Copyright © 2019 Munters Europe AB
Bruksanvisning i original
Innehållsförteckning
1. Inledning ........................................................................................................................... 5
1.1. Copyright ................................................................................................................ 5
1.2. Om handboken ....................................................................................................... 5
2. Styrsystem ........................................................................................................................ 6
2.1. Allmänt ................................................................................................................... 6
2.2. Alternativ för fuktighetsreglering ............................................................................... 6
2.2.1. Börvärde för luftfuktighet ............................................................................... 6
2.2.2. Externt börvärde ........................................................................................... 6
2.3. Slingstyrenheter ...................................................................................................... 7
2.4. Givare .................................................................................................................... 8
2.5. Frekvensomriktare .................................................................................................. 8
3. Användargränssnitt ............................................................................................................ 9
3.1. Allmänt ................................................................................................................... 9
3.1.1. Starta/stoppa från styrsystemets panel .......................................................... 9
3.1.2. Startsidan .................................................................................................... 9
3.1.3. Inloggning .................................................................................................. 10
3.1.4. Main Index ................................................................................................. 10
3.2. Status ................................................................................................................... 11
3.3. Luftfuktighet .......................................................................................................... 12
3.3.1. Fuktighetsreglering ..................................................................................... 13
3.4. Larm .................................................................................................................... 14
3.4.1. Larmtyper .................................................................................................. 14
3.4.2. Återställa larm ............................................................................................ 14
3.4.3. Larmmeny .................................................................................................. 14
3.4.4. Larminställningar ........................................................................................ 15
3.4.5. Humidity deviation ...................................................................................... 15
3.4.6. Temperature deviation ................................................................................ 15
3.5. Inställningar .......................................................................................................... 16
3.5.1. Operating mode ......................................................................................... 16
3.5.2. Givare ....................................................................................................... 17
3.5.3. Remote ...................................................................................................... 17
3.5.4. Communication .......................................................................................... 18
3.5.5. Service ...................................................................................................... 18
3.5.6. HMI settings ............................................................................................... 18
3.5.7. Version ...................................................................................................... 18
3.5.8. Time & Date ............................................................................................... 18
4. Felsökning ....................................................................................................................... 19
AirC-styrsystem
3
1. Inledning
1.1. Copyright
Innehållet i denna handbok kan ändras utan föregående meddelande.
NOTERA
Den här handboken innehåller information som är skyddad av upphovsrättslagar. Det
är inte tillåtet att reproducera eller överföra någon del av denna handbok utan skriftligt
samtycke från Munters.
Munters Europe AB, P.O. Box 1150, SE-16426 KISTA Sweden
1.2. Om handboken
Denna kompletterande handbok innehåller viktig information och riktlinjer för användning av avfuktarens
styrsystem. Den måste användas ihop med avfuktarens användarhandbok eftersom de tillsammans ut-
gör den kompletta dokumentationen.
Mer information om avfuktaren finns i användarhandboken. Använd inte avfuktaren utan att även först
läsa användarhandboken.
Viktig användarinformation som till exempel avsedd användning och säkerhetsinformation finns också i
användarhandboken för avfuktaren.
NOTERA
Vissa av de alternativ som beskrivs är inte tillgängliga för alla typer av avfuktare.
AirC-styrsystem
5
2. Styrsystem
2.1. Allmänt
Detta avsnitt ger en översikt över hur man ställer in det avancerade inbyggda mikroprocessorbaserade
styrsystemet. Själva mikroprocessorn och tillhörande komponenter har redan konfigurerats på fabriken
för det aktuella användningsområdet, med undantag för hur nödvändig indata ska överföras till mikro-
processorn.
Vid leverans har styrsystemet redan konfigurerats med vissa standardinställningar. Dessa kan justeras
på plats under installationen och driftsättningen.
Mikroprocessorn hanterar övervakningen av utomhus- och inomhusmiljö. Baserat på denna information
kan sedan avfuktningen startas för att upprätthålla önskad inomhusmiljö.
Aggregatet kan vid behov styras och startas av ett BMS (Building Management System) via en anslut-
ning med Modbus-protokoll. Munters AirC-styrenhet har stöd för Modbus RTU via ett RS-485-gränssnitt
med 2/3 ledare och Modbus TCP/IP via Ethernet.
Det är också möjligt att styra enskilda funktioner direkt från en extern källa. En termostat/hygrostat eller
BMS används för att sända signalerna för att aktivera aggregatet.
Om den här styrmetoden används är det fortfarande mikroprocessorn som övervakar och skyddar de
interna funktionerna.
Munters AirC-styrsystem består av styrenheten, en kontrollpanel och flera givare. Styrenheten drivs av
en 24 VAC-transformator.
Det finns fyra behörighetsnivåer:
Nivå 0: Alla driftinställningar och värden visas.
Nivå 1: Operatörsinloggning.
Nivå 2: Serviceinloggning.
Nivå 3: Systemkonfiguration.
2.2. Alternativ för fuktighetsreglering
Det finns två möjligheter till fuktighetsreglering. Valt alternativ ställs in när aggregatet konfigureras.
2.2.1. Börvärde för luftfuktighet
Aggregatet styrs efter ett internt inställbart börvärde som kan ha ett av tre möjliga format:
relativ luftfuktighet i procent (%RH)
beräknad daggpunkt (temperatur)
beräknad absolut luftfuktighet (g/kg)
Börvärdet kan ställas in från kontrollpanelen, via Modbus-kommunikation eller en analog insignal från
en extern källa. Den analoga insignalen kan konfigureras som 0–20 mA, 4–20 mA eller 0–10 V.
2.2.2. Externt börvärde
Regenereringsvärmaren styrs direkt av en extern analog signal på 0–20 mA, 4–20 mA eller 0–10 V.
Denna metod gör att aggregatets avfuktningskapacitet kan ställas in på en effekt mellan 0 och 100 %.
Insignalen konverteras sedan till ett börvärde för styrning av värmaren.
AirC-styrsystem
6
2.3. Slingstyrenheter
Styrsystemets slingstyrenheter arbetar för att upprätthålla börvärdena för luftfuktighet och regenerering-
stemperatur.
Hysteresgränser kan ställas in för luftfuktigheten för att tillåta variationer runt börvärdet inom specifika
gränser innan aggregatet startas eller stängs av.
I nedanstående bild avser de angivna värdena följande:
%RH Relativ luftfuktighet
SP Börvärde
H+ Övre hysteresgräns
H- Nedre hysteresgräns
Figur 1. Hysteres
%RH
SP
H+
H-
Om luftfuktigheten överskrider den övre hysteresgränsen (Hyst Start) kommer avfuktaren att starta och
påbörja reglering mot börvärdet.
Regleringen fortsätter så länge luftfuktighetsvärdet ligger över den nedre hysteresgränsen (Hyst Stop).
Avfuktaren stannar inte förrän luftfuktighetsvärdet faller under den nedre hysteresgränsen.
Den startar igen nästa gång värdet överskrider den övre gränsen.
AirC-styrsystem
7
2.4. Givare
Nedan följer exempel på givare som kan användas för att inhämta information till styrenheten.
Regenereringstemperatur
Våtluftstemperatur
Retur- eller rumstemperatur
Retur- eller rumsluftfuktighet
Rotorrotation
Tryckbrytare regenereringsluftfilter
Tryckbrytare processfilter
2.5. Frekvensomriktare
Frekvensomriktare används för att reglera elmotorns varvtal. De ersätter motorns kontaktorer och över-
lastreläer och fungerar som mjukstartare för motorn. Frekvensomriktaren kan också identifiera problem
som t.ex. högt amperetal, och stänger i så fall av motorn för att skydda den och indikerar ett feltillstånd.
AirC-styrsystem
8
3. Användargränssnitt
3.1. Allmänt
3.1.1. Starta/stoppa från styrsystemets panel
Tryck på start/stopp-knappen längst upp till höger för att använda aggregatet.
Tryck en gång i avstängt läge för att gå till automatikläget med givarstyrning.
Håll in i tre sekunder eller mer i avstängt eller automatiskt läge för att gå till manuellt läge, avfuktning
med 100 % kapacitet.
Tryck en gång i automatiskt eller manuellt läge för att gå till avstängt läge.
3.1.2. Startsidan
Startsidan visar följande information:
Luftfuktighet
Temperatur
Regenereringstemperatur
Driftläge
Aggregatets status
Larmstatus, larm och information
Tryck på
eller för att gå till Main Index.
AirC-styrsystem
9
3.1.3. Inloggning
Lösenord för användarinloggning är 1111.
Ange lösenord
Tryck på
och för att välja position.
Tryck på
och för att ändra siffran.
Tryck på för att bekräfta PIN-koden.
Tryck på för att gå till startsidan.
3.1.4. Main Index
Välj ikon för önskad meny och tryck på .
NOTERA
Information om standardinställningar finns i det aggregatspecifika rapportdokumentet.
AirC-styrsystem
10
3.2. Status
Välj ikon och tryck på .
Ingen inloggning krävs.
NOTERA
Innehållet i menyerna kan variera beroende på konfiguration.
Alternativ Värden Enhet
Operating mode Start Up Delay*Alarm*Off*Automatic*Manual
Unit status Off*Off-Alarm*Waiting*Standby*Starting*Run-
ning*Stopping
Operating type Sensor*Full capacity*External heater control
Remote start On*Off
Relative humidity 0.0... 100.0 %RH
Dewpoint -60.0... +60.0 °C
Absolute humidity 0.0... 20.0 g/kg
Humidity setpoint 0.0... 100.0 %RH
Dewpoint setpoint -60.0... +60.0 °C
Floating setpoint Givarvärde + kompensation °C
Humidity setpoint 0.0... 20.0 g/kg
Humidity setpoint (re-
mote)
0.0... 100.0 %RH
Dewpoint setpoint (re-
mote)
-60.0... +60.0 °C
Humidity setpoint (re-
mote)
0.0... 20.0 g/kg
Temperature -64.0... 200.0 °C
React temperature -64.0... 200.0 °C
Wet air temperature -64.0... 200.0 °C
Surface temperature -64.0... 200.0 °C
AirC-styrsystem
11
Alternativ Värden Enhet
Ext heater signal 0.0... 100.0 %
Calculated heater set-
point
0... 150 °C
React max temperatu-
re
-64.0... 200.0 °C
Heater output 0... 100 %
React fan On*Off
Process fan On*Off
Rotor On*Off
Time left for service 0... 32000 Timmar
Time left for service 0... 1000 Dagar
Log out
3.3. Luftfuktighet
Välj ikon och tryck på .
Lösenord på användarnivå eller högre krävs.
NOTERA
Innehållet i menyerna kan variera beroende på konfiguration.
Alternativ Värden Enhet
Relative humidity 0.0... 100.0 %RH
Dewpoint -60.0... +60.0 °C
Absolute humidity 0.0... 20.0 g/kg
Humidity setpoint 0.0... 100.0 %RH
Dewpoint setpoint -60... +60 °C
Humidity setpoint 0.0... 20.0 g/kg
AirC-styrsystem
12
Alternativ Värden Enhet
Humidity setpoint (re-
mote)
0.0... 100.0 %RH
Dewpoint setpoint (re-
mote)
-60... +60 °C
Humidity setpoint (re-
mote)
0.0... 20.0 g/kg
Surface temperature -64.0... 200.0 °C
Floating setpoint Givarvärde + kompensation °C
Floating setpoint off-
set
-10.0... +10.0 °C
Humidity hysteresis
start
-10.0... +10.0 %RH
Humidity hysteresis
stop
-10.0... +10.0 %RH
Dewpoint hysteresis
start
-10.0... +10.0 °C
Dewpoint hysteresis
stop
-10.0... +10.0 °C
Humidity hysteresis
start
-10.0... +10.0 g/kg
Humidity hysteresis
stop
-10.0... +10.0 g/kg
Remote start Off*On
Ext. heater signal 0.0... 100.0 %
Start limit 0.0... 100.0 %
Relative humidity 0.0... 100.0 %RH
Force limit start 0... 100 %RH
Force limit hyst. -10.0... 0.0 %RH
Humidity controller >
Operating type Sensor*Full capacity*External heater control
Log out
3.3.1. Fuktighetsreglering
Alternativ Värden Enhet
Controller output 0... 100 %
Humidity P-factor 0.00... 20.00
Humidity I-time 0... 3600 sek.
Humidity D-time 0... 3600 sek.
Humidity sample rate 1... 60 sek.
Humidity startup value 0... 100 %
AirC-styrsystem
13
3.4. Larm
3.4.1. Larmtyper
Styrsystemet kan avge två typer av meddelanden:
Larm – stoppar hela aggregatet. Måste återställas manuellt.
Information – varning eller indikering om att service krävs.
3.4.2. Återställa larm
Gå till larmmenyn med knapparna på kontrollpanelen.
Larmlistan visar alla aktiva larm.
Återställ alla aktiva larm efter att ha åtgärdat problemen: Välj Acknowledge All Alarms > Yes och tryck
på ENTER. Lösenord på användarnivå eller högre krävs.
3.4.3. Larmmeny
Välj ikon och tryck på
.
Ingen inloggning krävs.
Välj listan över aktiva larm eller larmhistoriklistan, det senaste larmet visas först.
Alternativen Acknowledge all alarms och Alarm settings kräver inloggning på användarnivå eller högre.
Välj Acknowledge för att återställa aktiva larm efter att ha åtgärdat problemen.
AirC-styrsystem
14
3.4.4. Larminställningar
NOTERA
Innehållet i menyerna kan variera beroende på konfiguration.
Alternativ Värden Enhet
Humidity deviation >
Temperature deviation >
React filter clogged, delay 0... 3600 sek.
Process filter clogged, delay 0... 3600 sek.
Sensor fault react temp, delay 0... 300 sek.
Sensor fault wet air temp, delay 0... 300 sek.
Sensor fault surface temp, delay 0... 300 sek.
Sensor fault humidity sensor 1, delay 0... 300 sek.
Sensor fault humidity sensor 2, delay 0... 300 sek.
Sensor fault temp sensor 1, delay 0... 300 sek.
Sensor fault temp sensor 2, delay 0... 300 sek.
Process fan fault, delay 0... 60 sek.
React fan fault, delay 0... 60 sek.
Rotor fault, delay 0... 60 sek.
Rotor stopped, delay 0... 3600 sek.
Heater fault, delay 0... 60 sek.
Long cooling time, delay 0... 3600 sek.
Clear alarm history Cancel*Reset
Log out
3.4.5. Humidity deviation
Alternativ Värden Enhet
Humidity deviation type Disabled*High limit*Low li-
mit*Both
Delay 0... 300 min.
High limit 0.0... 100.0 %RH
Low limit -100.0... 0.0 %RH
3.4.6. Temperature deviation
Alternativ Värden Enhet
Temperature deviation type Disabled*High limit*Low li-
mit*Both
Delay 0... 300 min.
High limit -100.0... 100.0 °C
Low limit -100.0... 100.0 °C
AirC-styrsystem
15
3.5. Inställningar
Välj ikon och tryck på .
NOTERA
Innehållet i menyerna kan variera beroende på konfiguration.
Operating mode >
Sensors >
Remote >
Communication >
Service >
HMI settings >
Version >
Time & Date >
3.5.1. Operating mode
Fan mode >
Timer >
Fan mode
Alternativ Värden Enhet
Process fan mode On demand*Continuous*Intermit
Intermit interval 1... 120 min.
Intermit run time 1... 30 min.
AirC-styrsystem
16
Timer
Alternativ Värden Enhet
Timer Disabled*Enabled
Timer status Off*On
Start time 00:00 tt:mm
Stop time 00:00 tt:mm
3.5.2. Givare
Alternativ Värden Enhet
Operating type Sensor*Full capacity*External heater control
Control type Relative*Dewpoint calc*Absolute calc
Humidity sensor 1
type
Disabled*0-10V*0-20mA*4-20mA*Modbus
Humidity sensor 1 min 0... 100 %RH
Humidity sensor 1
max
0... 100 %RH
Humidity sensor 2
type
Disabled*0-10V*0-20mA*4-20mA*Modbus
Humidity sensor 2 min 0... 100 %RH
Humidity sensor 2
max
0... 100 %RH
Control sensor Sensor 1*Sensor 2*Average*Minimum*Maxi-
mum
Temp sensor 1 type Disabled*0-10V*0-20mA*4-20mA*Modbus
Temp sensor 1 min -80... 200 °C
Temp sensor 1 max -80... 200 °C
Temp sensor 2 type Disabled*0-10V*0-20mA*4-20mA*Modbus
Temp sensor 2 min -80... 200 °C
Temp sensor 2 max -80... 200 °C
Temp control sensor Sensor 1*Sensor 2*Average*Minimum*Maxi-
mum
Restart
3.5.3. Remote
Alternativ Värden Enhet
External start Disabled*Enabled
Humidity control type Sensor*Full capacity*External heater control
External heater con-
trol type
Disabled*0-10V*0-20mA*4-20mA
Remote setpoint type Disabled*0-10V*0-20mA*4-20mA
Remote setpoint min -100... 100 %RH /
°C / g/kg
Remote setpoint max -100... 100 %RH /
°C / g/kg
Restart
AirC-styrsystem
17
3.5.4. Communication
TCP/IP
Alternativ Värden Enhet
IP address
Netmask
Gateway
Use DHCP Active*Passive
Restart
Modbus
Alternativ Värden Enhet
Slave ID 1... 247
Baud rate 9600*19200*38400
Data + Stop bits 8+1*8+2
Parity None*Even*Odd
Termination Active*Passive
Restart
3.5.5. Service
Endast för servicetekniker.
Inloggning på rätt nivå krävs.
3.5.6. HMI settings
Alternativ Värden Enhet
Start view Simple*Advanced
Screen saver Yes*No
Screen saver delay 1... 60 min.
Auto logout delay 1... 60 min.
3.5.7. Version
Alternativ
Unit type
Fabrication number
Software version
3.5.8. Time & Date
Alternativ
Set date
Set time
AirC-styrsystem
18
4. Felsökning
NOTERA
Andra larmindikeringar kan förekomma. Kontakta i så fall Munters service.
Symptom Indikering Möjlig orsak Åtgärd
Aggregatet har
stannat.
Displayen är
släckt.
Strömtillförseln bruten. Kontrollera strömförsörjning-
en till aggregatet.
En säkring och/eller strömb-
rytare har löst ut.
Ta reda på orsaken till felet
och vidta lämpliga åtgärder.
Återställ säkringen och/eller
strömbrytaren.
Om felet återkommer, kon-
takta Munters service.
Aggregatet står i
läge AUTO och
har stannat.
Displayen är
tänd.
Det finns inget behov av av-
fuktning.
Driftläget är STANDBY
Kontrollera om aktuell luftfuk-
tighetsnivå är lägre än inställt
börvärde.
Ställ in börvärdet så att det
är lägre än aktuell luftfuktig-
hetsnivå för att se om aggre-
gatet startar.
Kontrollera att värdet från
fuktighetsgivaren är korrekt.
Fjärrstart är inte ansluten.
Driftläget är WAITING.
Kontrollera att kablaget för
fjärrstartsfunktionen är kor-
rekt draget.
Kontrollera att ingången är
bryggad.
Aggregatet har
stannat.
Den röda larm-
lampan på opera-
törspanelen blin-
kar.
Följande text vi-
sas på displayen:
Process fan fault Bristfällig strömförsörjning Kontrollera flöden, fläktmotor
och strömbrytare.
Åtgärda eventuella fel, åter-
ställ strömbrytaren.
React fan fault
Rotor fault Överhettad drivmotor; rotorn
rör sig trögt.
Kontrollera motor, drivning
och rotortätningar. Återställ
strömbrytaren.
Rotor stopped Fel på drivrem. Kontrollera drivremmens
spänning och skick. Kontrol-
lera rotationsgivaren för ro-
torn.
AirC-styrsystem
19
Symptom Indikering Möjlig orsak Åtgärd
Heater fault Luftflödet är för litet. Något
av överhettningsskydden har
löst ut, antingen på grund av
blockering av regenerering-
sluftflödet eller på grund av
att regenereringsluftflödet är
för lågt inställt.
Kontrollera att luftflödet är
korrekt enligt användarhand-
boken.
Återställ motorns strömbryta-
re.
Fel på regenereringsvärma-
re.
Återställ säkringen och/eller
strömbrytaren. Om felet åter-
kommer, kontakta Munters
service.
Sensor fault
React Temperatu-
re
Temperaturen ligger utanför
givarens gränser.
Kontrollera givarens funktion.
Sensor fault Wet
Air Temperature
Sensor fault Sur-
face Temperature
Sensor fault Tem-
perature Sensor
Sensor fault Hu-
midity Sensor
Luftfuktigheten ligger utanför
givarens gränser.
Gul informations-
symbol på skär-
men.
Följande text vi-
sas på displayen:
React filter clog-
ged
Inloppsfiltret är igensatt Inspektera och byt filter vid
behov
Process filter
clogged
Time for service Serviceräknaren har nått för-
inställd servicetid.
Kontakta Munters för att
boka ett servicebesök.
Sensor Fault Hu-
midity Sensor 1
Relativ luftfuktighetsgivare 1
ligger utanför givarens grän-
ser
Kontrollera givarens funktion.
Sensor Fault Hu-
midity Sensor 2
Relativ luftfuktighetsgivare 2
ligger utanför givarens grän-
ser
Sensor Fault
Temperature 1
Temperaturgivare 1 ligger
utanför givarens gränser
Sensor Fault
Temperature 2
Temperaturgivare 2 ligger
utanför givarens gränser
Too long cooling
time
Kyltemperaturen uppnås inte
inom inställd tid
Kontrollera luftflöde och vär-
mare.
Humidity devia-
tion
Uppmätt luftfuktighet avviker
mer från luftfuktighetsbörvär-
det än vad de förinställda
gränserna medger
Återställ larmet.
Temperature de-
viation
Temperaturavvikelsen ligger
inte inom förinställda gränser
Aggregatet går
men luftfuktighe-
ten minskar inte.
Humidity devia-
tion
Regenererings- och process-
luftflödena avviker från nomi-
nella luftflöden.
Mät och justera regenerer-
ings- och processluftflödena
enligt användarhandboken.
AirC-styrsystem
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24